Aquarea Heat Pump Manager (HPM) – Manual Part 1: Installation and Commissioning – 12/2014
Commissioning
8
Example 2: Loading with changing opening times
Heating circuit 1 should be in operation during the opening times of the storing; the non-
occupation period applies outside the opening times.
Opening hours:
Monday to Friday from 08:00 to 12:00 and from 13:00 to 20:00 hours
Saturday from 09:00 to 15:00 hours
Closed on Sundays
Procedure:
►
Open timer channel
HeatC1
as described before.
►
Using the
[▼]
button, select the
Week programme
submenu.
► Confirm using the
[OK]
button.
► Perform the following settings and confirm using the
[OK]
button:
Name
Information text
Standard
setpoint
Settings for
this example
Remark
group
0: none 1: Mo-Thur 2:
Mo-Fr 3: Mo-Sun
0
2
if group = 2, then uniform
times are from Monday
to Friday
mo numOT
Monday number OT
2
2
mo beg OT1
Monday begin OT1
00:00
08:00
mo end OT1
Monday end OT1
24:00
12:00
mo beg OT2
Monday begin OT2
– –:– –
13:00
mo end OT2
Monday end OT2
– –:– –
20:00
sa numOT
Saturday number OT
2
1
sa beg OT1
Saturday begin OT1
00:00
09:00
sa end OT1
Saturday end OT1
24:00
15:00
su numOT
Sunday number OT
2
0
For Monday to Friday, a group with uniform occupation times was set; for
Saturday only one occupation time was set with a different start and end.
Times outside the specified time periods are considered non-occupation periods
with a corresponding reduction of the room temperature setpoint.