Aquarea Heat Pump Manager (HPM) – Manual Part 1: Installation and Commissioning – 12/2014
Commissioning
8
Parameter for extended configuration
Menu
Functions
Description, terminal assignment and settings
Extended configur.
HCu1 room compensation
Optimization of the heating circuits by the switching
on room thermostat, room temp sensor and remote
setpoint transmitter
HCu2 room compensation
HP Bivalence
Boiler release (alternative/parallel) during outside
temperatures below the limit or demand
Strategy addHS
Cascade with additional (3. / 4.) heat source (boiler
release), switch-on delay during full output
Domestic hot water Solar
Solar loading in domestic hot water tank
Buffer Solar
Solar loading in buffer tank (heating)
Buffer addHS/fireside
Add. heat source (Pellet boiler) / water bag in fire-
place for buffer tank (heating)
Photovoltaics
Use of self-generated surplus energy for domestic
hot water, heating / cooling (buffer load)
Smart Grid
Operating state is controlled by energy supplier:
1: Restriction of the heat pump (ESP restriction)
2: Automatic (no effect)
3: Percent increase of current demand
4: Maximum operation (Max-load)
The functions of the system parts have their own sub-menus allocated to them. The sub-menus
are only displayed, if the respective system part belongs to the loaded system diagram.
Example: If a system diagram with only one heating circuit is loaded, then the sub-menu for
heating circuit 2
hCu2 room compens.
, is not shown.
The following steps are required to activate the functions:
●
Allocate the required input or output terminals
● Depending on function, set a specific operating mode
●
Perform settings on the work parameters
The functions for extended configuration and their parameters are described in more detail in
the following sections.
Notice
Detailed description of functions and parameters: →
HPM Manual Part 2
.
hCux room compensation
With this function, heating circuits (hCu1 or hCU2) can be optimized in two ways:
●
Switching off via the room thermostat when reaching the setpoit
● Correction of the flow setpoint calculation by means of the measured value of a
room temperature sensor
i