Aquarea Heat Pump Manager (HPM) – Manual Part 1: Installation and Commissioning – 12/2014
Easy Setup Overview
3
Step 6
Perform settings for “Domestic hot water”
Name
Information text
Standard
setpoint
Remark
6-1
SP-OT1
Setpoint OT1*
50 °C
is always used when no other tem-
perature setpoints for domestic hot
water are available or apply.
6-2
SP-OT2
Setpoint OT2*
50 °C
Use during timer function
6-3
SP-NO
Setpoint NO*
2.0 °C
Use during timer function, e.g. night-
time lowering
6-4
maxSP
max. setpoint tank temperature 70 °C
accept this value when activating
therm. disinfection
6-5
maxDemFl-T max. flow temp. requirement
70 °C
accept this value when activating
therm. disinfection
6-6
thermDes
Therm. Disinfection 0: no 1:
Automatic
0
if 6-6 thermDes = 1 (autom. therm. Dis.):
6-6.1 SP-DHWta
Tank setpoint Therm.Disinfec-
tion
70 °C
Setpoint for domestic hot water tank
1
6-6.2 SP-loadFl
Loading flow setpoint therm.
disinfection
85 °C
Setpoint is transferred to the HP
during the thermal disinfection
6-6.3 day
0: daily 1-7: Monday-Sunday
1
Day for thermal disinfection
6-6.4 time
Time start thermal disinfection 01:00
6-6.5 maxDuration maximum duration therm.
disinfection
240 min
Time within which the setpoint temp.
in tank must be reached, otherwise:
error message
6-6.6 thermDOn
Therm. Disinfection relay
output BoosterH
0
assign free output terminal, such as
terminal 11; release for additional
heat source or signal contact, max.
load of terminal: 1 A
* OT = occupation time; NO = Non-occupation time
1 If the temperature setpoint for the domestic hot water tank has not been reached during the thermal disinfection, then
the respective message is displayed. If this message output should be suppressed, go to the menu
MCR-BMS
»
domestic hot water
» Function
» Message
and set the parameter
ThermDes
to
0
.
Perform advanced settings for the “Domestic hot water”, if solar system is installed
Name
Information text
Standard setpoint
Remark
6-7
TDiffSolOn
Temp. difference solar pump on 8.0 K
6-8
TDiffSolOff
Temp. difference solar pump off 2.0 K
6-9
maxTSolTa
max. temperature solar tank
sensor
70 °C
6-10 maxTcoll
max. temperature collector
sensor
110 °C
6-11 collFrLim
Frost.lim collector
–10.0 °C
→
HPM Manual Part 2, Chapter 5: Domestic hot water