SVC 820-Tankless Gas Trouble Shooting Manual Page |
77
77
65 – Error Code Diagnostic Chart
YES
NO
YES
YES
NO
While water is flowing and unit is
attempting to ignite; check DC Voltage
across White & Black Wires at
connector “C”:
8 – 16 DC VOLTS
Is the DC voltage
OK?
Attempt to operate unit again.
If the unit malfunctions due to an Error
Code 65:
Replace Control Board
Is the DC voltage
OK?
Turn power to unit OFF then ON again and turn water
flow on. Check DC Voltage across Red & Black Wires
at connector “C”:
8 – 16 DC VOLTS
Turn power to unit OFF then ON again and turn water
flow on. Check DC Voltage across Green & Black
Wires at connector “C”:
4 – 6 DC VOLTS
Attempt to operate unit again.
If the unit malfunctions due to an Error
Code 65:
Replace Control Board
Is the DC voltage
OK?
NO
Attempt to operate unit again.
If the unit malfunctions due to an Error
Code 65:
Replace Control Board
Attempt to operate unit again.
If the unit malfunctions due to an Error
Code 65:
Replace Water Control Valve
Summary of Contents for PH2-20R DVSN
Page 158: ... 158 Schematic Disassembly PH2 20RDVS PH2 25RDVS PH2 28RDVS ...
Page 159: ... 159 Schematic Disassembly PH2 20RDVS PH2 25RDVS PH2 28RDVS ...
Page 160: ... 160 Schematic Disassembly PH2 20RDVS PH2 25RDVS PH2 28RDVS ...
Page 162: ... 162 Schematic Disassembly PH2 20ROF PH2 25ROF PH2 28ROF ...
Page 163: ... 163 Schematic Disassembly PH2 20ROF PH2 25ROF PH2 28ROF ...
Page 164: ... 164 Schematic Disassembly PH2 20ROF PH2 25ROF PH2 28ROF ...
Page 166: ...Schematic Disassembly PHH 32RDV PHH 25RDV 166 ...
Page 167: ...Schematic Disassembly PHH 32RDV PHH 25RDV 167 ...
Page 169: ... 169 Schematic Disassembly PHH 32ROF PHH 25ROF ...