SVC 820-Tankless Gas Trouble Shooting Manual Page |
59
59
29 – Error Code
Explanation:
High Efficiency Condensing Units ONLY:
Condensate Drain is NOT draining.
Diagnostic Checks:
•
Plug not removed from condensate drain
•
Pinch in condensate drain line
•
Blockage in condensate drain line
•
Drain line has unnecessary “P” trap
CONDENSATE DRAIN DIAGNOSTICS:
Ensure you removed the condensate protection plug
located at bottom of unit.
1
Check your condensate drain line for internal or external
blockage. Make sure drain line is NOT pinched.
2
Drain Line