4-1
Section
Controller
37
Settings
Use the provided screwdriver to make switch settings as shown below.
Node Number Settings
DIP Switch Settings
Default Set Values
The following table shows default set values.
Switch
Name
Default
setting
Meaning
SW1
Node number (10’s digit)
0
Node number 00
SW2
Node number (1’s digit)
0
SW3-1
Communications format setting
OFF
BCC mode
SW3-2
Communications sync setting
OFF
No sync
SW3-3
OFF
SW3-4
OFF
SW3-5
Low power consumption setting
OFF
Normal mode
SW3-6
Communications distance setting
OFF
Long-distance mode
SW3-7
V700-CD1D-V3
Not used
OFF
Not used
V700-CD2D-V3
RS-485 termination
resistance setting
OFF
Not terminated
SW3-8
Termination resistance setting
OFF
Not terminated
SW4-1
Baud rate setting
OFF
9,600 bps
SW4-2
OFF
SW4-3
Data length setting
OFF
7 (ASCII7)
SW4-4
Parity bit setting
OFF
Even
SW4-5
OFF
SW4-6
Stop bit length setting
OFF
2
SW4-7
Communications mode setting
OFF
No ACK/NACK control
SW4-8
Time-out setting
OFF
See note. (500 ms)
Note The pin 8 setting of SW4 will be meaningless if pin 7 is set to OFF.
SW3 (left)
SW4 (right)