50
(n050 to n056) are the same
2. If the following conditions are not satisfied in the V/f pat-
tern setting:
Max. Output Frequency (n011)
≥
Max. Voltage Output
Frequency (n013)
>
Mid. Output Frequency
(n014)
≥
Min. Output Frequency
(n016)
Note: Mid. Output Frequency (n014) is also used for
motor 2 settings, n014 has to be lower than n140 and
n147.
For details, refer to
Adjusting Torque According to Appli-
cation
(
V/f Pattern Setting
) on page 51.
3. If the following conditions are not satisfied in the jump
frequency settings:
Jump Frequency 3 (n085)
≤
Jump Frequency 2 (n084)
≤
Jump Frequency 1 (n083)
4. If the Frequency Reference Lower Limit (n034)
≤
Fre-
quency Reference Upper Limit (n033)
5. If the Motor Rated Current (n036)
≤
150% of Inverter rated
current
6. If one of the Acceleration/Deceleration Time settings
(n019 to n022) exceeds 600.0 sec. and it is tried to set
n018 to 1 (Acceleration/Deceleration Time Unit 0.01 sec).