106
14
Search Command from maxi-
mum frequency
Speed Search Command sig-
nal
83
15
Search Command from set
frequency
83
16
Acceleration/Deceleration
Hold Command
84
17
LOCAL/REMOTE selection
58
18
Communications/control cir-
cuit terminal selection
110
19
Emergency stop fault,
NO contact input
Inverter stops for an emergen-
cy stop signal input according
to the Stopping Method Selec-
tion (n005). When coast to
stop (n005 = 1) is selected,
the Inverter coasts to stop.
Digital Operator displays
(flashing).
-
20
Emergency stop alarm,
NO contact input
-
21
Emergency stop fault,
NC contact input
-
22
Emergency stop alarm,
NC contact input
-
23
PID control cancel
161
24
PID integral reset
161
25
PID integral hold
161
26
Inverter overheat alert
(OH3 alarm)
When the Inverter overheat
signal turns ON,
(flash-
ing) is displayed at the Digital
Operator.
-
27
Acceleration/deceleration
time selection 2
72
28
Motor Switching Command
(Motor Selection)
94
29
Bi-directional PID prohibit
(ON: Prohibited)
157
30
Frequency offset input 1
80
31
Frequency offset input 2
80
32
Frequency offset input 3
80
Setting
Name
Description
Ref.
page