118
Using Output Signals
(n057, n058, n059)
The functions of multi-function output terminals MA, MB, P1 and P2
can be changed as necessary by setting constants n057, n058, and n059.
• Terminal MA and MB functions: Set in n057
• Terminal P1 function: Set in n058
• Terminal P2 function: Set in n059
Setting
Name
Description
Ref.
page
0
Fault
Closed when Inverter fault occurs.
-
1
Operating
Closed when either FWD/REV Run
Command is input or voltage is output
from the Inverter.
-
2
Frequency agree
Closed when the set frequency agrees
with Inverter output frequency.
119
3
Zero speed
Closed when Inverter output frequency
is less than minimum output frequency.
-
4
Frequency detection 1
Output frequency
≥
Frequency Detec-
tion Level (n095)
77
5
Frequency detection 2
Output frequency
≤
Frequency Detec-
tion Level (n095)
77
6
Overtorque detection,
NO contact output
-
76
7
Overtorque detection,
NC contact output
-
76
8
Undertorque detected,
NO contact output
-
179
9
Undertorque detected,
NC contact output
-
179
10
Minor fault
Closed when an alarm has been de-
tected.
-
11
Base blocked
Closed when the Inverter output is
OFF.
-
12
Operating mode
Closed when LOCAL is selected for the
LOCAL/REMOTE selection.
-
13
Inverter operation
ready
Closed when an Inverter fault is not de-
tected, and operation is ready.
-
14
Fault retry
Closed during fault retries.
-