6 Programming Features
85
Time Chart for Acceleration/Deceleration Hold Command
Input
Note: If a FWD (REV) Run Command is input at the same time as an Acceler-
ation/Deceleration Hold Command, the motor will not operate. How-
ever, if the Frequency Reference Lower Limit (n034) is set to a value
greater than or equal to the Min. Output Frequency (n016), the motor
will operate at the Frequency Reference Lower Limit (n034).
External Analog Monitoring(n066)
Selects to output either output frequency or output current to analog out-
put terminals AM-AC for monitoring.
Note: Enabled only when n065 is set to 0 (analog monitor output).
Setting
Description
0
Output frequency
1
Output current
2
Main circuit DC voltage
3
Torque monitor
4
Output power
5
Output voltage reference
6
Frequency reference monitor
7
PID Feedback Amount (10 V/Maxi-
mum Output Frequency in n011)
8
Data Output via Communications
(MEMOBUS register No.0007H)
(10 V/1000)
FWD (REV)
Run Command
Acceleration/
Deceleration
Hold Command
Frequency
Reference
Output
Frequency
Frequency
Agree
Signal