9 Specifications
235
• 200 V Class Single-phase
* Sets the value of the motor resistance for one phase.
• 400 V Class 3-phase
* Sets the value of the motor resistance for one phase.
No.
Name
Unit
Factory Setting
-
Inverter Capacity
kW
0.55 kW
1.1 kW
1.5 kW
2.2 kW
n036 Motor Rated Current
A
1.9
3.3
6.2
8.5
n105 Torque Compensation Iron Loss
W
4.2
6.5
11.1
11.8
n106 Motor Rated Slip
Hz
2.9
2.5
2.6
2.9
n107 Motor Line-to-neutral Resistance *
Ω
4.573
2.575
1.233
0.8
n108 Motor Leakage Inductance
mH
42.21
19.07
13.4
9.81
n110 Motor No-load Current
%
62
55
45
35
n159 Motor 2 Mid. Output
Frequency Voltage
V
12.0
12.0
12.0
12.0
n160 Motor 2 Min. Output
Frequency Voltage
V
12.0
12.0
12.0
12.0
No.
Name
Unit
Factory Setting
-
Inverter Capacity
kW
0.55kW 1.1 kW 1.5 kW 2.2 kW 3.0 kW 4.0 kW
n036 Motor Rated Current
A
1.0
1.6
3.1
4.2
7.0
7.0
n105 Torque Compensation Iron Loss
W
4.0
6.1
11.0
11.7
19.3
19.3
n106 Motor Rated Slip
Hz
2.7
2.6
2.5
3.0
3.2
3.2
n107 Motor Line-to-neutral Resistance *
Ω
19.08 11.22 5.044 3.244 1.514 1.514
n108 Motor Leakage Inductance
mH
168.8 80.76 53.25 40.03 24.84 24.84
n110 Motor No-load Current
%
63
52
45
35
33
33
n159 Motor 2 Mid. Output
Frequency Voltage
V
24.0
24.0
24.0
24.0
24.0
24.0
n160 Motor 2 Min. Output
Frequency Voltage
V
24.0
24.0
24.0
24.0
24.0
24.0