108
To select the 3-wire sequence, set terminal S3 (n052)
to 0.
Failure to observe this warning may result in injury.
LOCAL/REMOTE Selection (Setting: 17)
Select the operation reference from either the Digital Operator or from
the settings of the Run Command Selection (n003) and Frequency Ref-
erence Selection (n004). The LOCAL/REMOTE Selection can be used
only when stopped.
Open:
Run according to the setting of Run Command Selection
(n003) or Frequency Reference Selection (n004).
Closed: Run according to the frequency reference and Run Command
from the Digital Operator.
Example: Set n003=1, n004=2, n008=0.
Open:
Run according to the frequency reference from multi-function
input terminal FR and Run Command from multi-function
input terminals S1 to S7.
Closed: Run according to the potentiometer frequency reference and
Run Command from the Digital Operator.
Up/Down Commands (Setting: n056 = 34)
When the FWD (REV) Run Command is ON, acceleration/deceleration
is enabled by inputting the UP or DOWN signal from multi-function
input terminals S6 and S7 without changing the frequency reference.
Operation can thus be performed at the desired speed. When Up/Down
Commands are specified in n056, any function set in n055 is disabled,
terminal S6 is the input terminal for the Up Command, and terminal S7
is the input terminal for the Down Command.
Multi-function Input Termi-
nal S6 (Up Command)
Closed
Open
Open
Closed
Multi-function Input Termi-
nal S7 (Down Command)
Open
Closed
Open
Closed
Operation Status
Acceler-
ation
Decel-
eration
Hold
Hold
WARNING