6 Programming Features
173
Display List
Operator
Display
Description
Corrective Action
Lit: Constant copy function selection enabled.
-
Lit: READ selected.
Flashes: READ under execution.
-
Lit: Writing (COPY) selected.
Flashes: Writing (COPY) under execution.
-
Lit: VERIFY selected.
Flashes: VERIFY under execution.
-
Lit: Inverter capacity display selected.
-
Lit: Software No. display selected.
-
Lit: READ, COPY (writing), VERIFY complet-
ed.
-
Flashes: Attempt made to execute READ
while Constant Read Selection Pro-
hibit (n177) is set to 0.
Confirm the necessity to execute READ, then
set Constant Read Selection Prohibit (n177) to
1 to execute READ.
Flashes: The constant could not be read prop-
erly for READ operation. Or, a main
circuit low voltage is detected during
READ operation.
Confirm that the main circuit power supply
voltage is correct, then re-execute READ.
Flashes: A checksum error occurred in the
constant data stored in the Digital
Operator.
The constants stored in the Digital Operator
cannot be used.
Re-execute READ to store the constants in
the Digital Operator.
Flashes: The password for the connected In-
verter and that for the constant data
stored in the Digital Operator dis-
agree.
Example: Writing (COPY) from V7 IP65 to
VS mini J7
Check if the Inverters are the same product
series.
Flashes: No constant data stored in the Digital
Operator.
Execute READ.
Flashes: Attempt made to execute writing
(COPY) or VERIFY between different
voltage classes or different control
modes.
Check each voltage class and control mode.
Flashes: A main circuit low voltage was de-
tected during writing (COPY) opera-
tion.
Confirm that the main circuit power supply
voltage is correct, then re-execute writing
(COPY).
Lit: A checksum error occurred in the constant
data stored in the Inverter.
Initialize the constants. If an error occurs
again, replace the Inverter due to a failure of
constant memory element (EEPROM) in the
Inverter.
Flashes: Attempt made to execute COPY or
VERIFY between different Inverters
or different capacities.
Press
to continue the execution of
COPY or VERIFY. Press
to interrupt
the execution of COPY or VERIFY.
ENTER
STOP