Section 2
Installation and Wiring
Input and Output Lines
■
RESET Signal Input Precautions
• Make sure that the input voltage of the RESET signal does not exceed the maximum voltage (26.4 V).
If the maximum voltage is exceeded, the ID Controller may malfunction.
• To improve the noise immunity, separate the wiring of the input lines from high-voltage equipment or
power lines by at least 1 m.
■
Error Signal Input Precautions
• The maximum switching capacity of the output terminals is 100 mA at 24 VDC (+10%/
15%).
If a voltage or load that exceeds the maximum switching capacity is used, the ID Controller may
malfunction.
• Use an auxiliary relay (100 mA max. at 24 VDC) in the output circuit.
■
Pin Arrangement
Refer to
for more information on the external I/O port.
Pin No.
Name
1
RUN
2
BUSY
3
ERROR
4
OUT1
5
OUT2
6
COM_O
7
RST
8
TRG/IN1
9
TRG/IN2
10
COM_I
RESET input
24 VDC
24 VDC
To ERROR output
Terminal
No.
1
2
3
4
5
6
7
8
9
10
• Controller Terminal Arrangement