28
The User Program
Section 2-3
Usage:
Using the write command, write in advance the number of desired overwriting
operations onto the overwriting operation management area of the DC.
After writing data to the most frequently used address, renew the number of
overwriting operations in order to check the life of the EEPROM. The number
of overwriting operations is determined for each address by the DC specifica-
tions. Therefore, it is necessary to count the number of overwriting operations
of the most frequently used address. It is also possible to check the life of the
EEPROM without renewing the number of overwriting operations.
Command:
Subtracts an appropriate number [up to 255 (00FF)] from the data of the
address designated by the user in order to judge if the address has been
overwritten for the number of operations set by the user. If 0 ($0000) is sub-
tracted, only the life of the address will be checked. The number of command
data words is fixed to 5.
Note
Designate the first address on the EEPROM DC so that the terminator will be
@@@
0 to
@@@
5 or
@@@
8 to
@@@
D, otherwise an address error will result.
Renewal of the number of writing
operations/Life checking
Write
stage
Life check
stage
Data writing
Life checking
Writing the number of overwriting
operations
Initialization
stage
A
0
15
M
4
D
S
2
*
00
D
4
4
1
3
1
D
5
3
Management of the
number of writing
operations
Memory management command
R/W Head no. (fixed to 1)
Designates the first address of the
management area within the range 0000
through FFFF (see note).
Designates the number of subtracting
operations within the range 0000 through 00FF.
Terminator
Summary of Contents for SYSMAC C200H-IDS01-V1
Page 1: ...OPERATION MANUAL ID Sensor SYSMAC C200H IDS01 V1 IDS21 Cat No W153 E1 04...
Page 3: ...iv...
Page 5: ...vi...
Page 7: ...viii TABLE OF CONTENTS Glossary 89 Index 91 Revision History 95...
Page 9: ......
Page 15: ...xvi Application Precautions 5...
Page 25: ......
Page 95: ......
Page 97: ......
Page 99: ......
Page 103: ......
Page 109: ......
Page 111: ......
Page 114: ...SYSMAC C200H IDS01 V1 IDS21 ID Sensor Cat No W153 E1 04 OPERATION MANUAL...