8
System Connections
Section 1-5
The information in this table applies only when no other Special I/O Units are
mounted to other Racks (PC or Expansion I/O Racks) and the Units in this
table are mounted only to a Remote I/O Slave Rack.
When combining Units from groups A, B, C, and D, use the following formulae:
3A + B + 2C + 6D
≤
12
A + B + C + D
≤
8
A maximum of ten Units can be mounted to one Remote I/O Slave Rack.
However, when mounting ten Units, the NC211 Position Control Unit is
counted as two Units and, if a PC Link Unit is used, it is counted as one Unit.
Connecting the ID System
Refer to page 2 for an illustration of system connections.
Before connecting and wiring the ID Sensor Unit, turn OFF the power to the
PC.
Connect the R/W Head or Antenna to the ID Sensor Unit connector marked
“HEAD” or “Antenna”. (To disconnect the cable, pull while grasping the outer
ring of the cable; do not pull at an angle.)
Connecting the Handheld
Programming Console
Refer to
3-2 Monitoring
for information on connecting the Handheld Program-
ming Console.
The Next Step
Once you have completed installation of the ID Sensor system, turn to
SEC-
TION 2 Operation
for details on setup and operation.
A
B
C
D
High-speed
Counter, Position
Control Unit
(NC111/NC112),
ASCII Unit, Analog
I/O Unit, ID Sensor
Unit, Fuzzy Logic
Unit
High-density I/O
Units, Temperature
Control Units, Cam
Positioner Unit
Temperature
Sensor Unit, Voice
Unit
Position Control
Unit (NC211)
4 Units max.
---
---
---
---
8 Units max.
---
---
---
---
6 Units max.
---
---
---
---
2 Units max.
Summary of Contents for SYSMAC C200H-IDS01-V1
Page 1: ...OPERATION MANUAL ID Sensor SYSMAC C200H IDS01 V1 IDS21 Cat No W153 E1 04...
Page 3: ...iv...
Page 5: ...vi...
Page 7: ...viii TABLE OF CONTENTS Glossary 89 Index 91 Revision History 95...
Page 9: ......
Page 15: ...xvi Application Precautions 5...
Page 25: ......
Page 95: ......
Page 97: ......
Page 99: ......
Page 103: ......
Page 109: ......
Page 111: ......
Page 114: ...SYSMAC C200H IDS01 V1 IDS21 ID Sensor Cat No W153 E1 04 OPERATION MANUAL...