Combining
External Regeneration Resistors
Item
Regeneration absorption capacity
70 W
280 W
Combining external
regeneration
resistors
Note Use a combination with an absorption capacity larger than the average regenerative power (P
r
).
j
Dimensions (Unit: mm)
Thermal switch output
1.5 dia.
(0.3 mm
2
)
3 dia. (0.75 mm
2
)
Wiring External Regeneration Resistors
Remove the short bar from between the RG and JP terminals on the Regeneration Unit and connect the
resistor(s) between the P and RG terminals.
External regeneration resistor
Short bar
Note The thermal switch output must be connected in the same way as the ALM output from the Re-
generation Unit, i.e., so that power supply is broken when the contacts open. If a power interrup-
tion sequence based on the output is not included in the circuit, the Regeneration Unit may be
damaged.