![background image](http://html.mh-extra.com/html/omron/ns10-tv-series/ns10-tv-series_programming-manual_744520618.webp)
Section 5 Troubleshooting and Maintenance
5-2 Error Messages
5-11
NS Series Programming Manual
No. Message
Cause
Possible countermeasure
23
WARNING No. 23: Screen data file(s) is
not correct: Touch the screen to continue
and transfer screen data again.
The screen data in the
PT is damaged. (The PT
power supply was turned
OFF while screen data
was being transferred, or
a cable was discon-
nected.)
Touch the PT’s touch panel, and
after
connecting
is displayed at
the bottom right of the screen, or
after the message “No project
data is registered. Press OK but-
ton and download project data.” is
displayed, reattempt screen
transfer.
24
WARNING No. 24: The recovery
program in the inserted Memory Card is
not supported by the PT. Update the
recovery program, referring to NS Series
Setup Manual. To continue starting the
PT without executing the program, touch
the screen.
The recovery program
cannot be started
because the recovery
program installer in the
Memory Card that is
inserted in the PT is not
supported by the current
hardware version of the
PT.
Touch the screen to start the
system that is currently installed
in the PT (i.e., not the recovery
program). To start the recovery
program that is in the Memory
Card, you must update the
recovery program that is stored in
the Memory Card. To update the
program, install the CX-Designer
in a personal computer and then
select
Programs - OMRON -
CX-One – CX-Designer – How
to recover or update the
system program
from the
Window's Start Menu.
Summary of Contents for NS10-TV Series
Page 2: ......
Page 12: ...Contents vi NS Series Programming Manual ...
Page 48: ...Section 1 Overview 1 5 Procedure before Operation 1 35 NS Series Programming Manual ...
Page 592: ...Section 3 Using PTs 3 12 Function Key Settings NS15 Only 3 35 NS Series Programming Manual ...
Page 606: ...Section 4 Using Functions 4 1 Application 4 13 NS Series Programming Manual ...