2-5 Communications Address Settings
NS-series PTs have improved network functions and can communicate with multiple hosts. Host
names are registered for the connected hosts and any area in the host can be accessed by specifying
the host name and area.
With NS-series PTs, data required for display can be accessed and the words and bits that store the
entered data can be allocated from any area in the PLC.
The allocated words and bits are read from and written to directly, the display status changed for the
objects on the PT screen, and the PT status controlled or reported.
Refer to System Settings and Project Properties and Creating Functional Objects in the CX-Designer
Online Help for details on registering hosts and setting addresses.
Refer to the Host Connection Manual: Temp. Control, MemLink for details on connecting Temperature
Controllers. Refer to the Host Connection Manual: Multivendor Connection for details on connecting to
another company’s PLC.
2-5-1 Register
Host
Procedure
1. Select
PT – Comm. Setting
.
2. The Comm. Setting Dialog Box will be displayed.
3. Select the connection method being used for the host connection (Serial Port A, Serial Port B,
Ethernet, or Controller Link) and click the
Add Host
Button.
1
2
3
4
5
6
4. The host will be added. Make the host settings.
The host settings depend on the connection method. For details, refer to
System Setting and Project
Properties
in the online help of the CX-Designer.
N
N
N
o
o
o
t
t
t
e
e
e
♦
When the NSH Series is set as the PT model, do not set a host connection other than serial port A.
♦
If “/” characters are used in the host names of a project created in CX-Designer, the “/” characters
will be converted to “_” characters when the project is opened in CX-Designer.
♦
To delete a registered host, select the host in the Comm. Setting Dialog Box, and then click the
De-
lete Host
Button.
♦
To connect to the host using EtherNet/IP, select
Ethernet
in the Comm. Setting Dialog Box.
Summary of Contents for NS10-TV Series
Page 2: ......
Page 12: ...Contents vi NS Series Programming Manual ...
Page 48: ...Section 1 Overview 1 5 Procedure before Operation 1 35 NS Series Programming Manual ...
Page 592: ...Section 3 Using PTs 3 12 Function Key Settings NS15 Only 3 35 NS Series Programming Manual ...
Page 606: ...Section 4 Using Functions 4 1 Application 4 13 NS Series Programming Manual ...