Section 2 NS Series Functions
2-15 Data Logs
2-354
NS Series Programming Manual
Settings for Data Logging Group Registration
1. Select
PT – Data log
,
or click
the
Register Group
Button on the General Tab Page in the data log
Functional Object Properties Dialog Box, to display the Data Log Setting Dialog Box.
1
2. Click the
Add
Button in the Data Log Setting Dialog Box to display the Data Log Group Setting
Dialog Box.
2
3. Set the log timing. In this example, the sampling cycle is “1” (s).
4. De-select both
Save the data periodically
and
Save with Ring Buffer
.
5. Set the number of logging points. In this example, the logging period is 100 s and the sampling cy-
cle is 1 s, so the number of logging points to be set is “100” (100
÷
1 = 100).