![background image](http://html.mh-extra.com/html/omron/ns10-tv-series/ns10-tv-series_programming-manual_744520407.webp)
Section 2 NS Series Functions
2-15 Data Logs
2-358
NS Series Programming Manual
Operations on the NS Hardware
1. Insert the Memory Card into the NS hardware.
2. Start the NS hardware, which now has the project created using the procedures described in the
last section.
When address $B100 changes from OFF to ON, data is logged for 100 s (1 min 40 s).
When the
Start
icon is pressed, $B100 changes to ON and logging starts.
When the
Stop
icon is pressed, $B100 changes to OFF and logging stops.
To read saved data, press the
Read File
icon on the object while logging is stopped and select the de-
sired file from the pop-up menu.
Example 2: Allocation of an Externally Controlled Address (Serial A: CIO00100.00) to the
Specified Address
Serial A:
CIO00100.00
ON
OFF
Standard data
Measured data
Time
Numeral value
Display direction: Right
100 s
Setting Data Log File Output Formats
The method for setting data log file output formats is shown below.
1. Select
PT – System setting
to display the System Settings Dialog Box.
2. Click
the
History
Tab.
3. Set
Logfile Output Format
to “Vertical Axis: Time/ Horizontal Axis: Address.”
4. Set
the
Data Log/Broken-line History
to “Hold data of always logging (Data Log).”
Summary of Contents for NS10-TV Series
Page 2: ......
Page 12: ...Contents vi NS Series Programming Manual ...
Page 48: ...Section 1 Overview 1 5 Procedure before Operation 1 35 NS Series Programming Manual ...
Page 592: ...Section 3 Using PTs 3 12 Function Key Settings NS15 Only 3 35 NS Series Programming Manual ...
Page 606: ...Section 4 Using Functions 4 1 Application 4 13 NS Series Programming Manual ...