Section 2 NS Series Functions
2-8 Common Functional Object Functions
2-70
NS Series Programming Manual
1
2
3
4
5
No. Setting
Details
1 Comment
Sets comments for units (16 characters).
2 Unit
name
Sets the name of the unit (up to 8 characters).
3 Scale
Sets the magnification (approximately
±
1.175494351e-38 to approximately
±
3.40238). The magnification can be set in integers, decimals, and indices.
Fractions cannot be set.
4 Offset
Sets the offset value (approximately
±
1.175494351e-38 to approximately
±
3.40238).
5
Go to fixed
scale Button
Displays a pre-registered fixed scale (after unit No. 1001).
Editing Units and Scales
Double-click each item in the Unit & Scale Setting Dialog Box to edit the units and scales.
Example: When the address is set to $W1000, unit to mm, scale to 100, and offset value to 50:
$W1000 contents
Formula Display
value
0
50 + 0
×
100
50 mm
1
50 + 1
×
100
150 mm
2
50 + 2
×
100
250 mm
100
50 + 100
×
100
10,050 mm
R
R
R
e
e
e
f
f
f
e
e
e
r
r
r
e
e
e
n
n
n
c
c
c
e
e
e
♦
If a decimal with many digits is set as the scale, the test and PT display values may differ. The
contents of the address, however, will be the same.
♦
The scale for a thumbwheel switch must be set to a power of 10, and the offset must be set to 0. If
any other values are set, the thumbwheel switch many not operate properly.
Summary of Contents for NS10-TV Series
Page 2: ......
Page 12: ...Contents vi NS Series Programming Manual ...
Page 48: ...Section 1 Overview 1 5 Procedure before Operation 1 35 NS Series Programming Manual ...
Page 592: ...Section 3 Using PTs 3 12 Function Key Settings NS15 Only 3 35 NS Series Programming Manual ...
Page 606: ...Section 4 Using Functions 4 1 Application 4 13 NS Series Programming Manual ...