Errors When Downloading
Section 10-5
10-5 Errors When Downloading
10-5-1 Outline
An NE1A-series Controller or other Safety Device may return an error when
configuration data is downloaded to them. The cause of the error can be
determined from the error information displayed on the Network Configurator.
10-5-2 Error Messages and Countermeasures
Message displayed on the Network
Configurator
Countermeasure
Cannot be executed in the current mode.
A fatal error (Abort) (MS indicator flashes red) has occurred. Set the switches
correctly or execute reset (Out-of-Reset) to clear the configuration data.
The device is locked.
The configuration data is locked. (LOCK indicator is lit.) Release the lock.
The TUNID is different.
The device is waiting for a TUNID setting after being reset (NS indicator is flashing
green/red) or the TUNID of the Network Configurator is different from the device when
downloading. Use the following steps to check the setting.
1. Reset the device to default settings then download the parameters again. The net-
work number may, however, be different from other devices. If the Controller’s 7-seg-
ment display shows “d6” (A
Safety I/O Connection Establishment Failure
message
appears on the Error History Tab Page in the Network Configurator Monitor Device
Window) after the operating mode has been changed, use steps (2) or (3) to correct
the error.
2. Select
Network – Upload
in the Network Configurator. Unify the network numbers
and reset all devices to the default settings. Once reset, download the parameters to
all devices again.
3. Select
Network – Property
to display the Network Property Dialog Box in Network
Configurator then click the
Get from Network
Button in the Network Number Field.
If there are multiple network numbers, select one of these numbers to unify all to that
network number.
Privilege violation.
1. The password that is being used does not have the right to change the configuration.
Check to see if the password is correct.
2. An attempt was made to set Standalone Mode through a DeviceNet connection.
Con-
nect the Network Configurator via the USB connector and download the
configuration again.
Cannot be executed in the current
device mode.
Downloading from more than one Network Configurator at the same time. Wait until
other downloads have been completed.
Summary of Contents for NE1A-SCPU01 - 07-2009
Page 3: ...iv...
Page 9: ...x TABLE OF CONTENTS...
Page 11: ...xii...
Page 15: ...xvi...
Page 70: ...35 Installation Section 3 1 Top Top Bottom Bottom...
Page 72: ...37 Installation Section 3 1 3 1 3 Dimensions and Weight Dimensions NE1A SCPU01 V1...
Page 85: ...50 Wiring Section 3 2...
Page 123: ...88 Explicit Message Communications Section 4 7...
Page 141: ...106 Safety Outputs Section 5 4...
Page 257: ...222 Connection Status Tables Section 10 8...
Page 261: ...226 NE1A series Controller Replacement Section 11 2...
Page 264: ...229 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Page 266: ...231 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 267: ...232 Appendix A Local Output Setting Example...
Page 269: ...234 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 270: ...235 Appendix A Local Output Setting Example...
Page 273: ...238 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Page 275: ...240 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 276: ...241 Appendix A Local Output Setting Example...
Page 289: ...254...
Page 293: ...258 Index...