220
Connection Status Tables
Section 10-8
10-8-3 Connection Status for the NE1A-series Controller (Safety Slave
Function)
Status
Countermeasures
00:0001
Normal communications
The Safety I/O connection status is normal.
01:0001
Safety I/O Connection
Timeout
The Safety I/O connection has timed out. Check the following items.
• Do all nodes have the same baud rate?
• Is the cable length correct (trunk lines and branch lines)?
• Is the cable disconnected or slack?
• Is the terminating resistance only on both ends of the main line?
• Is there a lot of noise?
• Is the network bandwidth allocation suitable?
01:0106
Output Connection Owner
Error
The Safety Slave has previously established an output safety I/O connec-
tion with a Safety Master at a different node address.
Reset the Safety Slave to the default settings, and then download the
device parameters again.
Refer to
5-1-2 Setting Safety Connection Parameters
in the
DeviceNet
Safety System Configuration Manual (Z905)
for information on output con-
nection owners.
01:0109
Data Size Error
The Safety Slave I/O size set to the NE1A-series Safety Slave and the size
set under the Safety Master safety connection setting does not match. The
Safety Slave I/O setting may have been changed, so delete then re-regis-
ter the connections registered to the Safety Master.
01:0110
Unconfigured Device
The Safety Slave has not been configurated. Download the device param-
eters to the Safety Slave.
01:0111
EPI Error
The EPI set under the Safety Master safety connection setting is smaller
than the Safety Slave cycle time. The EPI must be longer than both the
Safety Master and the Safety Slave cycle times. Check the Safety Master
safety connection setting.
01:0113
No. of Connections Error
The setting exceeds the maximum number of safety I/O connections sup-
ported by the Safety Slave. Check the relevant Safety Master safety con-
nection
settings.
01:0114
Vendor ID or Product Code
Error
The device data (vendor ID or product code) for the device on the Configu-
rator and the device used in the actual system does not match.
• Use Safety Slave Verification (
Device
−
Parameter
−
Verify
) to check
that the device in the system and the device registered to the Safety Mas-
ter match.
• If they do match, delete then re-register the connections registered to the
Safety Master.
01:0115
Device Type Error
The device data (device type) for the device on the Configurator and the
device used in the actual system does not match.
• Use Safety Slave Verification (
Device
−
Parameter
−
Verify
) to check
that the device in the system and the device registered to the Safety Mas-
ter match.
• If they do match, delete then re-register the connections registered to the
Safety Master.
01:0116
Firmware Revision Error
The device data (firmware revision) for the device on the Configurator and
the device used in the actual system does not match.
• Use Safety Slave Verification (
Device
−
Parameter
−
Verify
) to check
that the device in the system and the device registered to the Safety Mas-
ter match.
• If they do match, delete then re-register the connections registered to the
Safety Master.
Summary of Contents for NE1A-SCPU01 - 07-2009
Page 3: ...iv...
Page 9: ...x TABLE OF CONTENTS...
Page 11: ...xii...
Page 15: ...xvi...
Page 70: ...35 Installation Section 3 1 Top Top Bottom Bottom...
Page 72: ...37 Installation Section 3 1 3 1 3 Dimensions and Weight Dimensions NE1A SCPU01 V1...
Page 85: ...50 Wiring Section 3 2...
Page 123: ...88 Explicit Message Communications Section 4 7...
Page 141: ...106 Safety Outputs Section 5 4...
Page 257: ...222 Connection Status Tables Section 10 8...
Page 261: ...226 NE1A series Controller Replacement Section 11 2...
Page 264: ...229 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Page 266: ...231 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 267: ...232 Appendix A Local Output Setting Example...
Page 269: ...234 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 270: ...235 Appendix A Local Output Setting Example...
Page 273: ...238 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Page 275: ...240 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 276: ...241 Appendix A Local Output Setting Example...
Page 289: ...254...
Page 293: ...258 Index...