Errors When Resetting
Section 10-6
10-6 Errors When Resetting
10-6-1 Outline
The NE1A-series Controller
may return an error response when it is reset.
The messages displayed on the Network Configurator can be used to identify
and correct the error.
10-6-2 Error Messages and Countermeasures
Message displayed on the
Network Configurator
Countermeasures
Cannot execute in current mode.
The specified reset cannot be executed in the current device status. Refer to
7-2-2 Reset Type and NE1A-series Controller Status
and change the oper-
ating mode or configuration lock status of the Controller. Then execute the
reset again.
The device has a different TUNID.
The device TUNID will be used to
reset.
Is that OK?
The TUNID saved to the device and the TUNID specified by Network Con-
figurator do not match. Check that the device node address matches and
execute the reset if it is OK to use the device TUNID.
Access error
The password used does not provide authority to change configurations.
Check that the correct password is being used.
The device cannot be accessed or
the device type or password is dif-
ferent.
1. The device has just been reset or the power cycled and the device is not
ready for communications (i.e., not online with the NS indicator flashing or
lit green.) Check that the device is communications ready then reset.
2. The device specified for reset may not support that service. Check that the
device node address is correct.
3. The configuration data is locked. (The LOCK indicator is lit.) Remove the
lock then execute the specified reset.
4. The device is performing safety I/O communications and cannot, there-
fore, execute the specified reset. Change the operating mode of the rele-
vant Safety Master to IDLE mode. Then execute the specified reset.
Connection failed.
Tried to reset a device on the DeviceNet network via the NE1A-series Con-
troller’s USB port, but connection failed. Check that power is turned ON to
the device and reset again.
If the above cause does not apply, noise or other factors may be making
communications unstable. Check the following items.
• Do all nodes have the same baud rate?
• Is the cable length correct (trunk lines and branch lines)?
• Is the cable disconnected or slack?
• Is the terminating resistance only on both ends of the main line?
• Is there a lot of noise?
Summary of Contents for NE1A-SCPU01 - 07-2009
Page 3: ...iv...
Page 9: ...x TABLE OF CONTENTS...
Page 11: ...xii...
Page 15: ...xvi...
Page 70: ...35 Installation Section 3 1 Top Top Bottom Bottom...
Page 72: ...37 Installation Section 3 1 3 1 3 Dimensions and Weight Dimensions NE1A SCPU01 V1...
Page 85: ...50 Wiring Section 3 2...
Page 123: ...88 Explicit Message Communications Section 4 7...
Page 141: ...106 Safety Outputs Section 5 4...
Page 257: ...222 Connection Status Tables Section 10 8...
Page 261: ...226 NE1A series Controller Replacement Section 11 2...
Page 264: ...229 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Page 266: ...231 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 267: ...232 Appendix A Local Output Setting Example...
Page 269: ...234 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 270: ...235 Appendix A Local Output Setting Example...
Page 273: ...238 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Page 275: ...240 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 276: ...241 Appendix A Local Output Setting Example...
Page 289: ...254...
Page 293: ...258 Index...