249
Appendix A
Setting and Monitoring Safety Output Terminals: Outputs (NE1A-SCPU02)
Explicit
message
Service
Function
Command
Response
Service
code
Class
ID
In-
stance
ID
At-
tribute
ID
Data size
Monitor Mode for
Terminal Mainte-
nance Information
Read
Reads the monitor mode of
maintenance information for
the output (1 to 8) specified by
the Instance ID.
0E hex
3B
hex
01 to 08
hex
65 hex
---
1 byte
00 hex: Total ON time
mode
01 hex: Contact opera-
tion counter
mode
Write
Writes the monitor mode of
maintenance information for
the output (1 to 8) specified by
the Instance ID.
10 hex
3B
hex
01 to 08
hex
65 hex
1 byte
00 hex: Total
ON time mode
01 hex: Contact
operation
counter mode
---
SV for Output Total
ON Time or
Contact Operation
Counter
Read
Reads the SV of the total ON
time (unit: seconds) or contact
operation counter (unit: opera-
tions) for the output (1 to 8)
specified by the Instance ID.
0E hex
3B
hex
01 to 08
hex
68 hex
---
4 bytes
0000 0000 to FFFF
FFFF hex
(0 to 4,294,967,295)
Write
Reads the SV of the total ON
time (unit: seconds) or contact
operation counter (unit: opera-
tions) for the output (1 to 8)
specified by the Instance ID.
10 hex
3B
hex
01 to 08
hex
68 hex
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295)
---
Read Output Total
ON Time or
Contact Operation
Counter
Read
Reads the total ON time (unit:
seconds) or contact operation
counter (unit: operations) for
the output (1 to 8) specified by
the Instance ID.
0E hex
3B
hex
01 to 08
hex
66 hex
---
4 bytes
0000 0000 to FFFF
FFFF hex
(0 to 4,294,967,295)
Reset Output Total
ON Time or
Contact Operation
Counter
Reset
Resets to 0 the total ON time
(unit: seconds) or contact oper-
ation counter (unit: operations)
for the output (1 to 8) specified
by the Instance ID.
05 hex
3B
hex
01 to 08
hex
66 hex
---
---
Read Monitor Sta-
tus of Output Total
ON Time or Contact
Operation Counter
Read
Reads the monitor status of the
total ON time or contact opera-
tion of the number (1 to 8)
specified by the Instance ID.
0E hex
3B
hex
01 to 08
hex
67 hex
---
1 byte
00 hex: In range
01 hex: Out of range
(over monitor value)
Read Safety Output
Normal Flag
Read
Reads the normal flag status of
the number (1 to 8) specified by
the Instance ID.
0E hex
3B
hex
01 to 08
hex
05 hex
---
1 byte
00 hex: Error
01 hex: Normal
Read Safety Output
Error Information
Cause
Read
Reads the cause for the normal
flag status of the number (1 to
8) specified by the Instance ID
being OFF (error).
0E hex
3B
hex
01 to 08
hex
6E hex
---
1 byte
00 hex: No error
01 hex: Invalid configu-
ration
02 hex: Overcurrent
detection
03 hex: Short-circuit
detection
04 hex: High constant
error
05 hex: Error in other
channel of dual
channels
06 hex: Internal relay
circuit error
07 hex: Relay error
08 hex: Data error
between dual
channel outputs
09 hex: Detection of
short circuit
between wires
Read AND of Safety
Output Normal
Flags
Read
Reads the logical AND of the
normal flag status for all out-
puts 1 to 8.
0E hex
3C
hex
01 hex
05 hex
---
1 byte
00 hex: Error
01 hex: All normal
Read OR of Moni-
tor Status of Output
Total ON Times or
Contact Operation
Counters
Read
Reads the logical OR of the
monitor status of the total ON
time or contact operation
counter for all outputs 1 to 8.
0E hex
3C
hex
01 hex
72 hex
---
1 byte
00 hex: All in range
01 hex: Output out of
range (over
monitor value)
Summary of Contents for NE1A-SCPU01 - 07-2009
Page 3: ...iv...
Page 9: ...x TABLE OF CONTENTS...
Page 11: ...xii...
Page 15: ...xvi...
Page 70: ...35 Installation Section 3 1 Top Top Bottom Bottom...
Page 72: ...37 Installation Section 3 1 3 1 3 Dimensions and Weight Dimensions NE1A SCPU01 V1...
Page 85: ...50 Wiring Section 3 2...
Page 123: ...88 Explicit Message Communications Section 4 7...
Page 141: ...106 Safety Outputs Section 5 4...
Page 257: ...222 Connection Status Tables Section 10 8...
Page 261: ...226 NE1A series Controller Replacement Section 11 2...
Page 264: ...229 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Page 266: ...231 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 267: ...232 Appendix A Local Output Setting Example...
Page 269: ...234 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 270: ...235 Appendix A Local Output Setting Example...
Page 273: ...238 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Page 275: ...240 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 276: ...241 Appendix A Local Output Setting Example...
Page 289: ...254...
Page 293: ...258 Index...