252
Appendix A
Setting and Monitoring Safety Output Terminals: Outputs (NE1A-SCPU01)
Monitoring Test Output Terminals: NE1A-SCPU01
Explicit message
Service
Function
Command
Response
Ser-
vice
code
Class
ID
In-
stance
ID
At-
trib-
ute ID
Data size
Read Safety
Output Normal
Flag
Read
Reads the normal flag status
of the number (1 to 8) speci-
fied by the Instance ID.
0E hex
3B
hex
01 to
08 hex
05 hex ---
1 byte
00 hex: Error
01 hex: Normal
Read Safety
Output Error
Information Cause
Read
Reads the cause for the nor-
mal flag of the number (1 to
8) specified by the Instance
ID being OFF.
0E hex
3B
hex
01 to
08 hex
6E hex ---
1 byte
00 hex: No error
01 hex: Invalid configuration
02 hex: Overcurrent detection
03 hex: Short-circuit detection
04 hex: High constant error
05 hex: Error in other channel of
dual channels
06 hex: Internal relay circuit
error
07 hex: Relay error
08 hex: Data error between dual
channel outputs
09 hex: Detection of short circuit
between wires
Read AND of
Safety Output
Normal Flags
Read
Reads the logical AND of the
normal flag status for all
outputs 1 to 8.
0E hex
3C
hex
01 hex
05 hex ---
1 byte
00 hex: Error
01 hex: All normal
Explicit message
Service
Function
Command
Response
Ser-
vice
code
Class
ID
In-
stance
ID
At-
trib-
ute ID
Data size
Read Test Output
Normal Flag
Read
Reads the normal flag status
of the test output (1 to 4)
specified by the Instance ID.
0E hex
307
hex
01 to
04 hex
68 hex ---
1 byte
00 hex: Normal
01 hex: Error
Read Test Output
Error Information
Cause
Read
Reads the cause for the
normal flag of the test output
(1 to 4) specified by the
Instance ID being OFF
(error).
0E hex
307
hex
01 to
04 hex
76 hex ---
1 byte
00 hex: No error
01 hex: Invalid configuration
02 hex: Overcurrent detection
05 hex: High constant error
06 hex: Undercurrent detection
Read OR of Test
Output Normal
Flags
Read
Reads the logical OR of the
normal flag status for all
outputs 1 to 4.
0E hex
308
hex
01 hex
69 hex ---
1 byte
00 hex: All normal
01 hex: Error
Summary of Contents for NE1A-SCPU01 - 07-2009
Page 3: ...iv...
Page 9: ...x TABLE OF CONTENTS...
Page 11: ...xii...
Page 15: ...xvi...
Page 70: ...35 Installation Section 3 1 Top Top Bottom Bottom...
Page 72: ...37 Installation Section 3 1 3 1 3 Dimensions and Weight Dimensions NE1A SCPU01 V1...
Page 85: ...50 Wiring Section 3 2...
Page 123: ...88 Explicit Message Communications Section 4 7...
Page 141: ...106 Safety Outputs Section 5 4...
Page 257: ...222 Connection Status Tables Section 10 8...
Page 261: ...226 NE1A series Controller Replacement Section 11 2...
Page 264: ...229 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Page 266: ...231 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 267: ...232 Appendix A Local Output Setting Example...
Page 269: ...234 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 270: ...235 Appendix A Local Output Setting Example...
Page 273: ...238 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Page 275: ...240 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 276: ...241 Appendix A Local Output Setting Example...
Page 289: ...254...
Page 293: ...258 Index...