About NE1A-series Safety Network Controllers
Section 1-1
1-1-2
Features of the NE1A-series Controllers
Safety Logic Operations
In addition to basic logic functions, such as AND and OR, function blocks such
as Emergency Stop or Safety Gate Monitoring that enable various safety
applications are supported.
Local Safety I/O
• In the NE1A-SCPU01(-V1), a total of 24 local safety I/O points are sup-
ported: 16 inputs and 8 outputs.
• In the NE1A-SCPU02, a total of 48 local safety I/O points are supported:
40 inputs and 8 outputs.
• Faults in external wiring can be detected.
• Dual Channel Mode can be set for pairs of related local input terminals.
When Dual Channel Mode is set, an NE1A-series Controller can evaluate
the input data patterns and the time discrepancy between input signals.
• Dual Channel Mode can be set for pairs of related local output terminals.
When Dual Channel Mode is set, an NE1A-series Controller can evaluate
the output data patterns.
DeviceNet Safety Communications
• As a Safety Master, Pre-Ver. 1.0 Controllers can perform safety I/O com-
munications with up to 16 connections using up to 16 bytes per connec-
tion.
• The NE1A-series Controllers with unit version 1.0 can perform safety I/O
communications with up to 32 connections using up to 16 bytes per con-
nection.
• As a Safety Slave, the NE1A-series Controllers can perform safety I/O
communications with a maximum of four connections using up to 16 bytes
per connection.
DeviceNet Standard Communications
As a Standard Slave, the NE1A-series Controllers can perform standard I/O
communications with one Standard Master for up to two connections using up
to 16 bytes per connection.
Standalone Controller Mode
An NE1A-series Controller can be used as a Standalone Controller by dis-
abling its DeviceNet communications.
Configuration with a Graphical Tool
• A graphical tool is provided for both network configuration and logic pro-
gramming. It enables easy configuration and programming.
• A Logic Editor can be activated from the Network Configurator.
• Configuration data can be downloaded and uploaded, and devices can be
monitored online via DeviceNet, USB, or the peripheral interface of an
OMRON PLC.
System Startup and Error Recovery Support
• The error information can be checked by using the Network Configurator
or the indicators on the front of the NE1A-series Controller.
• The NE1A-series Controllerís internal status information can be moni-
tored from a Standard PLC by allocating the information in the Standard
Master. In the same way, monitoring with a Safety PLC is possible by allo-
cating information in the Safety Master.
Summary of Contents for NE1A-SCPU01 - 07-2009
Page 3: ...iv...
Page 9: ...x TABLE OF CONTENTS...
Page 11: ...xii...
Page 15: ...xvi...
Page 70: ...35 Installation Section 3 1 Top Top Bottom Bottom...
Page 72: ...37 Installation Section 3 1 3 1 3 Dimensions and Weight Dimensions NE1A SCPU01 V1...
Page 85: ...50 Wiring Section 3 2...
Page 123: ...88 Explicit Message Communications Section 4 7...
Page 141: ...106 Safety Outputs Section 5 4...
Page 257: ...222 Connection Status Tables Section 10 8...
Page 261: ...226 NE1A series Controller Replacement Section 11 2...
Page 264: ...229 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Page 266: ...231 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 267: ...232 Appendix A Local Output Setting Example...
Page 269: ...234 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 270: ...235 Appendix A Local Output Setting Example...
Page 273: ...238 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Page 275: ...240 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 276: ...241 Appendix A Local Output Setting Example...
Page 289: ...254...
Page 293: ...258 Index...