58
Remote I/O Allocations
Section 4-3
4-3-2
Remote I/O Area Attributes
Remote I/O Area Attributes
The NE1A-series Controller’s remote I/O area has the following attributes.
All values in the safety remote I/O area will be cleared if the operating mode is
changed. If a communications error occurs, all data for the connection for
which the error occurred will be cleared.
Note
Refer to
Section 8 Operating Modes and Power Supply Interruptions
for
details on each operating mode.
Slave I/O Area Hold Setting
Mode change
Communications
error
Power ON
RUN
to Idle
RUN or Idle to
Configuration
Safety remote I/O
area (DeviceNet
Safety)
Cleared
(safety state)
Cleared
(safety state)
Cleared for con-
nection (safety
state)
Cleared
(safety state)
Standard remote
I/O area
(DeviceNet)
Depends on
Slave I/O area
hold setting.
Cleared
Depends on Slave
I/O area hold set-
ting.
Cleared
Setting
Description
Default
Validity
Clear
The slave output area (inputs to a user application program) is
cleared when a communications (connection) error occurs.
The slave input area (outputs to a Standard Master) is cleared
when the operating mode is changed to IDLE Mode.
Clear
When power
supply is cycled
Hold
The last data in the slave output area (inputs to a user application
program) is held when a communications (connection) error
occurs.
The last data in the slave input area (outputs to a Standard
Master) is held when the operating mode is changed to IDLE
Mode.
Values are cleared, however, when a critical error or abort occurs
or when the power supply is turned ON again.
Summary of Contents for NE1A-SCPU01 - 07-2009
Page 3: ...iv...
Page 9: ...x TABLE OF CONTENTS...
Page 11: ...xii...
Page 15: ...xvi...
Page 70: ...35 Installation Section 3 1 Top Top Bottom Bottom...
Page 72: ...37 Installation Section 3 1 3 1 3 Dimensions and Weight Dimensions NE1A SCPU01 V1...
Page 85: ...50 Wiring Section 3 2...
Page 123: ...88 Explicit Message Communications Section 4 7...
Page 141: ...106 Safety Outputs Section 5 4...
Page 257: ...222 Connection Status Tables Section 10 8...
Page 261: ...226 NE1A series Controller Replacement Section 11 2...
Page 264: ...229 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Page 266: ...231 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 267: ...232 Appendix A Local Output Setting Example...
Page 269: ...234 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 270: ...235 Appendix A Local Output Setting Example...
Page 273: ...238 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Page 275: ...240 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 276: ...241 Appendix A Local Output Setting Example...
Page 289: ...254...
Page 293: ...258 Index...