![background image](http://html1.mh-extra.com/html/omron/ne1a-scpu01-07-2009/ne1a-scpu01-07-2009_operation-manual_742749253.webp)
218
Connection Status Tables
Section 10-8
10-8-2 Connection Status for DST1 Series
Status
Countermeasure
00:0001
Normal communications
The Safety I/O connection status is normal.
01:0001
Safety I/O Connection
Timeout
The Safety I/O connection has timed out. Check the following items.
• Do all nodes have the same baud rate?
• Is the cable length correct (trunk lines and branch lines)?
• Is the cable disconnected or slack?
• Is the terminating resistance only on both ends of the main line?
• Is there a lot of noise?
• Is the network bandwidth allocation suitable?
01:0105
Configuration Owner Error The Safety Slave was configurated from a configuration tool or Safety
Master at a different node address last time. Reset the Safety Slave to the
default settings and download the device parameters again.
Refer to
5-1-2 Setting Safety Connection Parameters
in the
DeviceNet
Safety System Configuration Manual (Z905)
for information on configura-
tion owners.
01:0106
Output connection Owner
Error
The Safety Slave established output safety I/o connections with a Safety
Master at a different node address last time.
Reset the Safety Slave to the default settings and download the device
parameters again.
Refer to
5-1-2 Setting Safety Connection Parameters
in the
DeviceNet
Safety System Configuration Manual (Z905)
for information on output con-
nection owners.
01:0110
Device Not Configurated
The Safety Slave has not been configurated. Download the device param-
eters to the Safety Slave.
01:0113
No. of Connections Error
The setting for the number of safety I/O connections exceeds the upper
limit supported by the Safety Slave. Adjust the Safety Connection setting
for the relevant Safety Master.
01:0114
Vendor ID or Program
Code Error
The device data (vendor ID or product code) for the device on the Configu-
rator and the device used in the actual system does not match.
• Use Safety Slave Verification (
Device
−
Parameter
−
Verify
) to check
that the device in the system and the device registered to the Safety Mas-
ter match.
• If they do match, delete then re-register the connections registered to the
Safety Master.
01:0115
Device Type Error
The device data (device type) for the device on the Configurator and the
device used in the actual system does not match.
• Use Safety Slave Verification (
Device
−
Parameter
−
Verify
) to check
that the device in the system and the device registered to the Safety Mas-
ter match.
• If they do match, delete then re-register the connections registered to the
Safety Master.
01:0116
Revision Error
The device data (revision) for the device on the Configurator and the
device used in the actual system does not match.
• Use Safety Slave Verification (
Device
−
Parameter
−
Verify
) to check
that the device in the system and the device registered to the Safety Mas-
ter match.
• If they do match, delete then re-register the connections registered to the
Safety Master.
Summary of Contents for NE1A-SCPU01 - 07-2009
Page 3: ...iv...
Page 9: ...x TABLE OF CONTENTS...
Page 11: ...xii...
Page 15: ...xvi...
Page 70: ...35 Installation Section 3 1 Top Top Bottom Bottom...
Page 72: ...37 Installation Section 3 1 3 1 3 Dimensions and Weight Dimensions NE1A SCPU01 V1...
Page 85: ...50 Wiring Section 3 2...
Page 123: ...88 Explicit Message Communications Section 4 7...
Page 141: ...106 Safety Outputs Section 5 4...
Page 257: ...222 Connection Status Tables Section 10 8...
Page 261: ...226 NE1A series Controller Replacement Section 11 2...
Page 264: ...229 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Page 266: ...231 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 267: ...232 Appendix A Local Output Setting Example...
Page 269: ...234 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 270: ...235 Appendix A Local Output Setting Example...
Page 273: ...238 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Page 275: ...240 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 276: ...241 Appendix A Local Output Setting Example...
Page 289: ...254...
Page 293: ...258 Index...