246
Appendix A
Monitoring Test Output Terminals: NE1A-SCPU01-V1
Explicit
message
Service
Function
Command
Response
Service
code
Class
ID
In-
stance
ID
At-
tribute
ID
Data size
Monitor Mode for
Terminal Mainte-
nance Information
Read
Reads the monitor mode of
maintenance information of the
test output (1 to 4) specified by
the Instance ID.
0E hex
307
hex
01 to 04
hex
83 hex
---
1 byte
00 hex: Total ON time
mode
01 hex: Contact opera-
tion counter
mode
Write
Writes the monitor mode of
maintenance information of the
test output (1 to 4) specified by
the Instance ID.
10 hex
307
hex
01 to 04
hex
83 hex
1 byte
00 hex: Total
ON time mode
01 hex: Contact
operation
counter mode
---
SV for Test Output
Total ON Time or
Contact Operation
Counter
Read
Reads the SV of the total ON
time (unit: seconds) or contact
operation counter (unit: opera-
tions) for the input (1 to 4) spec-
ified by the Instance ID.
0E hex
307
hex
01 to 04
hex
86 hex
---
4 bytes
0000 0000 to FFFF
FFFF hex
(0 to 4,294,967,295)
Write
Writes the SV of the total ON
time (unit: seconds) or contact
operation counter (unit: opera-
tions) for the input (1 to 4)
specified by the Instance ID.
10 hex
307
hex
01 to 04
hex
86 hex
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295)
---
Read Test Output
Total ON Time or
Contact Operation
Counter
Read
Reads the total ON time (unit:
seconds) or contact operation
counter (unit: operations) for
the input (1 to 16) specified by
the Instance ID.
0E hex
307
hex
01 to 04
hex
84 hex
---
4 bytes
0000 0000 to FFFF
FFFF hex
(0 to 4,294,967,295)
Reset Test Output
Total ON Time or
Contact Operation
Counter
Reset
Resets to 0 the total ON time
(unit: seconds) or contact
operation counter (unit: opera-
tions) for the test output (1 to 4)
specified by the Instance ID.
05 hex
307
hex
01 to 04
hex
84 hex
---
---
Read Monitor
Status of Test
Output Total ON
Time or Contact
Operation Counter
Read
Reads the monitor status of the
total ON time or contact opera-
tion counter of the test output (1
to 4) specified by the Instance
ID.
0E hex
307
hex
01 to 04
hex
85 hex
---
1 byte
00 hex: In range
01 hex: Out of range
(over monitor
value)
Read Test Output
Safety Flag
Read
Reads the normal flag status
for the test output (1 to 4)
specified by the Instance ID.
0E hex
307
hex
01 to 04
hex
68 hex
---
1 byte
00 hex: Normal
01 hex: Error
Read Test Output
Error Information
Cause
Read
Reads the cause for the normal
flag of the test output (1 to 4)
specified by the Instance ID
being OFF (error).
0E hex
307
hex
01 to 04
hex
76 hex
---
1 byte
00 hex: No error
01 hex: Invalid
configuration
02 hex: Overcurrent
detection
05 hex: High constant
error
06 hex: Undercurrent
detection
Read OR of Test
Output Safety Flags
Read
Reads the logical OR of the
normal flag status for all test
outputs 1 to 4.
0E hex
308
hex
01 hex
69 hex
---
1 byte
00 hex: All normal
01 hex: Error
Read OR of
Monitor Status of
Test Output Total
ON Times or
Contact Operation
Counters
Read
Reads the logical OR of the
monitor status of the total ON
time or contact operation
counter for all test outputs 1 to
4.
0E hex
308
hex
01 hex
72 hex
---
1 byte
00 hex: All in range
01 hex: Test output out
of range (over
monitor value)
Summary of Contents for NE1A-SCPU01 - 07-2009
Page 3: ...iv...
Page 9: ...x TABLE OF CONTENTS...
Page 11: ...xii...
Page 15: ...xvi...
Page 70: ...35 Installation Section 3 1 Top Top Bottom Bottom...
Page 72: ...37 Installation Section 3 1 3 1 3 Dimensions and Weight Dimensions NE1A SCPU01 V1...
Page 85: ...50 Wiring Section 3 2...
Page 123: ...88 Explicit Message Communications Section 4 7...
Page 141: ...106 Safety Outputs Section 5 4...
Page 257: ...222 Connection Status Tables Section 10 8...
Page 261: ...226 NE1A series Controller Replacement Section 11 2...
Page 264: ...229 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Page 266: ...231 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 267: ...232 Appendix A Local Output Setting Example...
Page 269: ...234 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 270: ...235 Appendix A Local Output Setting Example...
Page 273: ...238 Appendix A Local Input and Test Output Setting Example Local Output Setting Example...
Page 275: ...240 Appendix A Programming Example Local Input and Test Output Setting Example...
Page 276: ...241 Appendix A Local Output Setting Example...
Page 289: ...254...