78
Chapter
4
Wiring
F3SG-4RA-25-02TS
User’s Manual
Wiring/Installation
4-5-4. Functional Earth Connection
The F3SG-R operates properly without functional earth connection in a general industrial environment.
If the F3SG-R fails due to electrical noise, connecting the F3SG-R to the functional earth may work to
prevent the noise. It is recommended the functional earth terminal of the F3SG-R be connected to
functional earth cables. Connection with protective earth cables may cause the F3SG-R to fail due to a
noise level of the environment.
When you connect the F3SG-R with the functional earth, connect an earth cable to the functional earth
terminals, as shown below.
The size of the screws of the terminals is M3. Make sure to use crimp terminals that fits the size.
The earth cable must have a cross section of 1 mm
2
or more with conductor resistance of 0.058 ohms/
m or less and a length of 20 m or less.
Bottom view of F3SG-R
Power Cable
Functional earth terminal (M3)
Do not loosen these screws.
Summary of Contents for F3SG-R Series
Page 19: ...xvii F3SG 4RA 25 02TS User s Manual Introduction E 7 4 Revision History 107...
Page 20: ...xviii Introduction F3SG 4RA 25 02TS User s Manual...
Page 52: ...32 Chapter 3 End Cap F3SG 4RA 25 02TS User s Manual Setting with Rotary Switch and End Cap...
Page 112: ...92 Chapter 6 Maintenance Checklists F3SG 4RA 25 02TS User s Manual Checklists...