5 Communications Data for Modbus
E5@C Digital Temperature Controllers Communications Manual (H175)
5-
1 Variab
le Area (Set
tin
g
Ran
g
e)
List
5
0500
2500
Operation/Adjustment
Protect
H'00000000 (0):
No restrictions in operation and adjustment levels
H'00000001 (1):
Move to adjustment level is prohibited.
H'00000002 (2):
Display and change of only “PV” and “PV/SP”
parameters is allowed.
H'00000003 (3):
Display of only “PV” and “PV/SP” parameters is
allowed.
Protect
0502
2501
Initial
Setting/Communications
Protect
H'00000000 (0):
Move to initial setting/communications setting
level is allowed. (Move to advanced function
setting level is displayed.)
H'00000001 (1):
Move to initial setting/communications setting
level is allowed. (Move to advanced function
setting level is not displayed.)
H'00000002 (2):
Move to initial setting/communications setting
level is prohibited.
0504
2502
Setting Change Protect
H'00000000 (0): OFF (Changing of setup on controller display is
allowed.)
H'00000001 (1): ON (Changing of setup on controller display is
prohibited.)
0506
2503
PF Key Protect
H'00000000 (0): OFF
H'00000001 (1): ON
0508
2504
Move to Protect Level
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
050A
2505
Password to Move to
Protect Level
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
(Can only be set. The monitor value is always H’00000000.)
050C
2506
Parameter Mask Enable
H'00000000 (0): OFF
H'00000001 (1): ON
050E
2507
Changed Parameters
Only
H'00000000 (0): OFF
H'00000001 (1): ON
0600
2600
Manual MV
Standard Models
Standard control:
H'FFFFFFCE to H'0000041A (
−
5.0 to 105.0)
Heating and cooling control:
H'FFFFFBE6 to H'0000041A (
−
105.0 to 105.0)
Position-proportional Models
Close position-proportional control with the Direct Setting of
Position Proportional MV parameter set to ON:
H'FFFFFFCE to H'0000041A (
−
5.0 to 105.0)
Manual
control
0602
2601
Set Point
SP lower limit to SP upper limit
Operation
0604
2602
Remote SP Monitor
Remote SP lower limit
−
10% FS to Remote SP upper limit +10% FS
0608
2604
Heater Current 1 Value
Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
060A
2605
MV Monitor (Heating)
Standard control:
H'FFFFFFCE to H'0000041A
(
−
5.0 to 105.0)
Heating and cooling control: H'00000000 to H'0000041A
(0.0 to 105.0)
060C
2606
MV Monitor (Cooling)
H'00000000 to H'0000041A (0.0 to 105.0)
060E
2607
Valve Opening Monitor
H'FFFFFF9C to H'0000044C (
−
10.0 to 110.0): Measured opening
H'00000000 to H'000003E8 (0.0 to 100.0): Estimated opening*
*
You can use this selection only with the E5EC-PR
@
-8
@@
or E5AC-PR
@
-8
@@
. (The Digital Controller must be
manufactured in August 2014 or later (version 2.2 or higher).)
Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byte
mode
Summary of Contents for E5AC
Page 2: ......
Page 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Page 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Page 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Page 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Page 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...
Page 223: ......