![Omron E5AC Communications Manual Download Page 134](http://html1.mh-extra.com/html/omron/e5ac/e5ac_communications-manual_742553134.webp)
6 Programless Communications
6 - 20
E5@C Digital Temperature Controllers Communications Manual (H175)
Programless communications start operating after the power supply is turned ON or after the E5
@
C is
reset. They stop operating when the initial setting level is entered.
The following table gives the operation command codes that can be set.
For details on operation commands, refer to
You can check the operation of programless communications in the Communications Status in the
upload area.
The value of the Communications Status changes between 0 and 1 each time the upload area is
updated.
6-3-3
Range of Operation for Programless Communications
Levels
Programless communications
Operation level, adjustment level, manual control level,
monitor/setting item level, and protect level
Setting area 0
Operates
Initial setting level, communications setting level, advanced
function setting level, and calibration level
Setting area 1
Stops
6-3-4
Operation Command Codes
Operation command
Operation command code
Switch
RUN/STOP
0100
RUN
0101
STOP
Multi-SP
0200
SP 0
0201
SP 1
0202
SP 2
0203
SP 3
0204
SP 4
0205
SP 5
0206
SP 6
0207
SP 7
AT Execute/Cancel
0300
AT Cancel
0301
100% AT Execute
0302
40% AT Execute
Write Mode
0400
Backup Mode
0401
RAM Write Mode
Save RAM Data
0500
Save RAM Data
Software Reset
0600
Software Reset
Auto/Manual
0900
Automatic Mode
0901
Manual Mode
Alarm Latch Cancel
0C00
Alarm 1 Latch Cancel
0C01
Alarm 2 Latch Cancel
0C02
Alarm 3 Latch Cancel
0C03
Heater Burnout Latch Cancel
0C04
HS Alarm Latch Cancel
0C05
Alarm 4 Latch Cancel
0C0F
All Latch Cancel
SP Mode
0D00
Local SP Mode
0D01
Remote SP Mode
Invert Direct/Reverse
Operation
0E00
Do Not Invert
0E01 Invert
Program Start
1100
Reset
1101
Start
6-3-5
Confirming Operation of Programless Communications
Summary of Contents for E5AC
Page 2: ......
Page 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Page 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Page 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Page 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Page 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...
Page 223: ......