![Omron E5AC Communications Manual Download Page 36](http://html1.mh-extra.com/html/omron/e5ac/e5ac_communications-manual_742553036.webp)
2 CompoWay/F Communications Procedures
2 - 4
E5@C Digital Temperature Controllers Communications Manual (H175)
The following examples show the end code when a command did not end normally.
Example 1) Illegal Sub-address, No SID, and No Command Text
•
Command
•
Response
End code is “16” (sub-address error).
The sub-address error code is used because the sub-address error has a higher error detection
priority than the format error.
Example 2) No Command Text
•
Command
•
Response
The end code is “14” (format error).
Example 3) No Node Number Provided
•
Command
The node number is lacking one character.
•
Response
There is no response.
2-1-4
Communications Data
Communications
format
Set (monitor)
values
Negative values
Decimal point
CompoWay/F
8-digit hexadecimal 2's complement
Decimal point is removed and the result is
converted to hexadecimal.
Example conversion: 105.0
→
1050
→
H'0000041A
2-1-5
End Code Example
STX
0
A
ETX
BCC
Node number Sub-address
A
ETX
BCC
1
6
STX
0
Node number Sub-address
End code
STX
0
0
ETX
BCC
SID
0
Node number Sub-address
0
ETX
BCC
1
4
STX
0
Node number Sub-address
End code
STX
ETX
BCC
Summary of Contents for E5AC
Page 2: ......
Page 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Page 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Page 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Page 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Page 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...
Page 223: ......