![Omron E5AC Communications Manual Download Page 101](http://html1.mh-extra.com/html/omron/e5ac/e5ac_communications-manual_742553101.webp)
5 - 5
5 Communications Data for Modbus
E5@C Digital Temperature Controllers Communications Manual (H175)
5-
1 Variab
le Area (Set
tin
g
Ran
g
e)
List
5
*1
You can use this parameter only with the E5EC-PR
@
-8
@@
or E5AC-PR
@
-8
@@
. (The Digital Controller must be
manufactured in August 2014 or later (version 2.2 or higher).)
074A
2725
Heater Burnout Detection
2
H'00000000 to H'000001F4 (0.0 to 50.0)
Adjustment
074C
2726
Leakage Current 2
Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
Operation
074E
2727
HS Alarm 2
H'00000000 to H'000001F4 (0.0 to 50.0)
Adjustment
0750
2728
Soak Time Remain
H'00000000 to H'0000270F (0 to 9999)
Operation
0752
2729
Soak Time
H'00000001 to H'0000270F (1 to 9999)
Adjustment
0754
272A
Wait Band
H'00000000 (0): OFF
H'00000001 to H'0000270F
(0.1 to 999.9 for Temperature input)
(0.01 to 99.99 for Analog input)
0756
272B
Remote SP Input Shift
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
0758
272C
Remote SP input Slope
Coefficient
H'00000001 to H'0000270F (0.001 to 9.999)
0800
2800
Input Digital Filter
H'00000000 to H'0000270F (0.0 to 999.9)
Advanced
function
setting
0808
2804
Moving Average Count
H'00000000 (0): OFF
H'00000001 (1): 2 times
H'00000002 (2): 4 times
H'00000003 (3): 8 times
H'00000004 (4): 16 times
H'00000005 (5): 32 times
081A
280D
FB Moving Average
Count
*1
H'00000000 (0): OFF
H'00000001 (1): 2 times
H'00000002 (2): 4 times
H'00000003 (3): 8 times
H'00000004 (4): 16 times
H'00000005 (5): 32 times
Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byte
mode
Summary of Contents for E5AC
Page 2: ......
Page 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Page 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Page 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Page 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Page 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...
Page 223: ......