The set point (SP) of a slave can be calculated from the set point of the master as shown below. The
slave performs the calculation only during operation. The value is not written to the slave if it exceeds
the set point limiter.
During operation: Slave SP = Master SP
×
SP Slope + SP Offset
When stopped: Slave SP = Master SP
Communications Setting Level
Display condition: The Protocol Setting parameter must be set to
cmp
and the Communications Unit
No. parameter must not be set to 0 (0 = master).
*
The decimal point position depends on the Decimal Point parameter setting.
Parameter name
Displayed
characters
Setting range
Unit
Default
SP Slope
sps
0.001 to 9.999
None
1.000
SP Offset
spos
Temperature input:
−
199.9 to 999.9
Analog input:
−
1,999 to 9,999*
EU
0.0
Summary of Contents for E5AC
Page 2: ......
Page 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Page 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Page 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Page 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Page 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...
Page 223: ......