6 Programless Communications
6 - 12
E5@C Digital Temperature Controllers Communications Manual (H175)
There are 13 upload settings and 13 download settings.
Communications Setting Level
Display condition: The Protocol Setting parameter must be set to
fins
,
mcp4
, or
fxp4
.
*
This parameter cannot be used when the Protocol Setting parameter is set to
fxp4
.
Example of Changing a Setting:
To set the Alarm Value 3 parameter for Download Setting 11, you would change the set value from 45
(Heater Burnout Detection 1) to 38 (Alarm Value 3).
6-2-8
Upload Settings and Download Settings
Parameter name
Displayed characters
Setting range
Default
Upload Setting 1
up 1
0 to 98
1
Communications Monitor
Upload Setting 2
up 2
2
Status (Upper Word)
Upload Setting 3
up 3
3
Status (Lower Word)
Upload Setting 4
up 4
4
Status 2 (Upper Word)
Upload Setting 5
up 5
6
Decimal Point Monitor
Upload Setting 6
up 6
7
Process Value
Upload Setting 7
up 7
8
Internal Set Point
Upload Setting 8
up 8
11
Heater Current 1 Value
Monitor
Upload Setting 9
up 9
16
MV Monitor (Heating)
Upload Setting 10
up10
0
Nothing assigned.
Upload Setting 11
up11
0
Nothing assigned.
Upload Setting 12
up12
0
Nothing assigned.
Upload Setting 13*
up13
0
Nothing assigned.
Download Setting 1
dn 1
30 to 98
31
Set Point
Download Setting 2
dn 2
61
Proportional Band
Download Setting 3
dn 3
62
Integral Time
Download Setting 4
dn 4
63
Derivative Time
Download Setting 5
dn 5
32
Alarm Value 1
Download Setting 6
dn 6
33
Alarm Value Upper Limit 1
Download Setting 7
dn 7
34
Alarm Value Lower Limit 1
Download Setting 8
dn 8
35
Alarm Value 2
Download Setting 9
dn 9
36
Alarm Value Upper Limit 2
Download Setting 10
dn10
37
Alarm Value Lower Limit 2
Download Setting 11
dn11
45
Heater Burnout Detection 1
Download Setting 12
dn12
57
Process Value Input Shift
Download Setting 13
dn13
75
SP Ramp Set Value
Summary of Contents for E5AC
Page 2: ......
Page 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Page 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...