![Omron E5AC Communications Manual Download Page 124](http://html1.mh-extra.com/html/omron/e5ac/e5ac_communications-manual_742553124.webp)
6 Programless Communications
6 - 10
E5@C Digital Temperature Controllers Communications Manual (H175)
Communications Setting Level
Display condition: The Protocol Setting parameter must be set to
fins
,
mcp4
, or
fxp4
.
Note: 1 The First Address Upper Word and First Address Lower Word parameters together specify the first
address.
Example:
(1) If the first address of the PLC is 123456, set the First Address Upper Word parameter to
12 and the First Address Lower Word parameter to 3456 in the E5
@
C.
(2) If you use an area labeled with “*1,” convert the first address of the PLC (hexadecimal) to
a decimal number and set the decimal value in the E5
@
C.
If the first address of the PLC is 12345, set the First Address Upper Word parameter to 7
and the First Address Lower Word parameter to 4565 in the E5
@
C.
2 Set the same first address in all of the E5
@
C Controllers (e.g., set the same value as the value that is set
for the E5
@
C with communications unit number 0).
Applicable PLC Memory Addresses
Parameter name
Displayed characters
Setting range
Default
Area
area
•
When Protocol Setting Parameter Is Set to FINS
0
0:
DM
1:
EM0
2:
EM1
3:
EM2
4:
EM3
5:
EM4
6:
EM5
7:
EM6
8:
EM7
9:
EM8
10: EM9
11: EMA
12: EMB
13: EMC
14: EMD
15: EME
16: EMF
17: EM10
18: EM11
19: EM12
20: EM13
21: EM14
22: EM15
23: EM16
24: EM17
25: EM18
•
When Protocol Setting Parameter Is Set to MCP4
0: D data registers
1: W link registers
*1
2: R file registers
3: ZR file registers
*1
4 to 25: D data registers
•
When Protocol Setting Parameter Is Set to FXP4
0: D data registers (DM
data memory registers)
1: None (W link registers)
*1
2: R expansion registers
(FM file registers)
3 to 25: Do not use.
Device names in parentheses are for Keyence
KV-series PLCs.
First Address Upper
Word
adrh
0 to 99
0
First Address Lower
Word
adrl
0 to 9999
0
Protocol setting
Area
Applicable address range
*2
Host Link (FINS)
DM
0 to 32767
EM0 to EM18
MC protocol (format 4)
D data registers
0 to 12287
W link registers
0 to 8191 (1FFF hex)
R file registers
0 to 32767
ZR file registers
0 to 999999 (F423F hex)
Dedicated protocol (format 4)
D data registers
DM data memory registers
*1
0 to 7999
W link registers
*1
0 to 16383 (3FFF hex)
R expansion registers
FM file registers
*1
0 to 9999
Summary of Contents for E5AC
Page 2: ......
Page 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Page 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Page 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Page 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Page 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...
Page 223: ......