![Omron E5AC Communications Manual Download Page 57](http://html1.mh-extra.com/html/omron/e5ac/e5ac_communications-manual_742553057.webp)
3 - 3
3 Communications Data for CompoWay/F
E5@C Digital Temperature Controllers Communications Manual (H175)
3-1 Variab
le Area (
S
et
tin
g
Ra
nge)
List
3
Note: The alarm function can also be used in Digital Temperature Controllers that do not have any auxiliary
outputs. In this case, confirm alarm occurrences via the status data.
Variable
type
Address
Parameter name
Setting (monitor) value
Level
C1 (81)
0000
Operation/Adjustm
ent Protect
H'00000000 (0): No restrictions in operation and
adjustment levels
H'00000001 (1): Move to adjustment level is
prohibited.
H'00000002 (2): Display and change of only "PV"
and "PV/SP" parameters is allowed.
H'00000003 (3): Display of only "PV" and "PV/SP"
parameters is allowed.
Protect
C1 (81)
0001
Initial
Setting/Communic
ations Protect
H'00000000 (0): Move to initial
setting/communications setting
level is allowed. (Move to advanced
function setting level is displayed.)
H'00000001 (1): Move to initial
setting/communications setting
level is allowed. (Move to advanced
function setting level is not
displayed.)
H'00000002 (2): Move to initial
setting/communications setting
level is prohibited.
C1 (81)
0002
Setting Change
Protect
H'00000000 (0): OFF (Changing of setup on
Controller display is allowed.)
H'00000001 (1): ON (Changing of setup on
Controller display is prohibited.)
C1 (81)
0003
Set Point
SP lower limit to SP upper limit
Operation
C1 (81)
0004
Alarm Value 1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
0005
Alarm Value Upper
Limit 1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
0006
Alarm Value Lower
Limit 1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
0007
Alarm Value 2
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
0008
Alarm Value Upper
Limit 2
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
0009
Alarm Value Lower
Limit 2
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
000A
Alarm Value 3
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
000B
Alarm Value Upper
Limit 3
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
000C
Alarm Value Lower
Limit 3
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
000D
Heater Burnout
Detection 1
H'00000000 to H'000001F4 (0.0 to 50.0)
Adjustment
C1 (81)
000E
SP 0
SP lower limit to SP upper limit
C1 (81)
000F
SP 1
SP lower limit to SP upper limit
C1 (81)
0010
SP 2
SP lower limit to SP upper limit
C1 (81)
0011
SP 3
SP lower limit to SP upper limit
C1 (81)
0012
Process Value
Input Shift
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
0013
PV Input Slope
Coefficient
H'00000001 to H'0000270F (0.001 to 9.999)
C1 (81)
0015
Proportional Band
H'0000001 to H'0000270F (0.1 to 999.9)
Summary of Contents for E5AC
Page 2: ......
Page 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Page 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Page 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Page 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Page 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...