6 Programless Communications
6 - 14
E5@C Digital Temperature Controllers Communications Manual (H175)
You can copy the settings of all parameters except for the Communications Unit No. parameter from
the master (i.e., the Controller with communications unit number 0) to one or more of the slaves (i.e.,
the Controllers with communications unit numbers other than 0). Copying parameters is possible only
between Controllers with the same model number and the same version. All of the slaves are automat-
ically reset after the copying operation is completed. Make sure that the system will not be adversely
affected before you copy parameter settings.
Communications Setting Level
Display condition: The Protocol Setting parameter must be set to
cmp
,
fins
,
mcp4
, or
fxp4
and the
Communications Unit No. parameter must be set to 0 (master).
Copying Procedure Starting from the Initial Status
(1) Connect the master and slaves with RS-485 connections and turn ON the power
supply.
(2) Set the Communications Unit No. parameters of the slaves in order starting from 1
and then return to the operation level.
(3) Set all of the parameters in the master except for those in the communications
setting level.
(4) Change the master to the communications setting level and change the
communications settings as given below.
Change the Protocol Setting parameter, set the Communications Unit No. parameter to 0,
set the Communications Baud Rate parameter to 19.2 for a Mitsubishi FX1 or FX2 PLC,
38.4 for a Mitsubishi FX3 PLC, and 57.6 for any other PLC, set the Send Data Wait Time
parameter to 1, and set the Highest Communications Unit No. parameter to the highest
communications unit number that is set.
Change the other parameters in the communications setting level as required.
Do not return to the operation level while you are changing the parameter settings. If you
mistakenly return to the communications setting level, return the Communications Baud
Rate parameter to 9.6, return to the operation level, and then set the Communications Baud
Rate parameter again.
6-2-9
Copying Parameter Settings
Case in which copying
is possible
The model numbers and versions are the same.
Example:E5CC-RX2ASM-002(V1.1)
→
E5CC-RX2ASM-002(V1.1)
Cases in which copying
is not possible
The model numbers are different.
Example:E5CC-
R
X2ASM-002
→
E5CC-
Q
X2ASM-002
The versions are different.
Example:E5CC-RX2ASM-002(V1.
1
)
→
E5CC-RX2ASM-002(V1.
0
)
Parameter name
Displayed
characters
Setting range
Default
Copy
copy
off
(Copying failed:
e0
**)
all
1 to 31
off
Summary of Contents for E5AC
Page 2: ......
Page 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Page 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Page 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Page 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Page 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...
Page 223: ......