3 - 11
3 Communications Data for CompoWay/F
E5@C Digital Temperature Controllers Communications Manual (H175)
3-1 Variab
le Area (
S
et
tin
g
Ra
nge)
List
3
*1
PRST (program start) can be set even when the program pattern is set to OFF, but the function will be
disabled.
*2
Selection is possible only if there is a remote SP input.
*3
Selection is possible only if external communications is supported.
*4
Do not set the same set value for more than one event input assignment.
Variable
type
Address
Parameter name
Setting (monitor) value
Level
C3 (83)
0016
Event Input
Assignment 1
*4
H'00000000 (0):
None
H'00000001 (1):
RUN/STOP
H'00000002 (2):
Auto/Manual Switch
H'00000003 (3):
Program Start
*1
H'00000004 (4):
Direct/Reverse Operation
H'00000005 (5):
SP Mode Switch
*2
H'00000006 (6):
100% AT Execute/Cancel
H'00000007 (7):
40% AT Execute/Cancel
H'00000008 (8):
Setting Change Enable/Disable
H'00000009 (9):
Communications Writing
Enable/Disable
*3
H'0000000A (10): Alarm Latch Cancel
H'0000000B (11): Multi-SP No. Switch, Bit 0
H'0000000C (12): Multi-SP No. Switch, Bit 1
H'0000000D (13): Multi-SP No. Switch, Bit 2
Initial
setting
C3 (83)
0017
Event Input
Assignment 2
*4
H'00000000 to H'0000000D (0 to 13)
Note: Same as for Event Input Assignment 1.
C3 (83)
0018
Event Input
Assignment 3
*4
H'00000000 to H'0000000D (0 to 13)
Note: Same as for Event Input Assignment 1.
C3 (83)
0019
Event Input
Assignment 4
*4
H'00000000 to H'0000000D (0 to 13)
Note: Same as for Event Input Assignment 1.
C3 (83)
001A
Number of
Multi-SP Points
H'00000001 (1): OFF
H'00000002 to H'00000008 (2 to 8)
Advanced
function
setting
C3 (83)
001B
SP Ramp Time
Unit
H'00000000 (0): EU/second
H'00000001 (1): EU/minute
H'00000002 (2): EU/hour
C3 (83)
001D
Standby Sequence
Reset
H'00000000 (0): Condition A
H'00000001 (1): Condition B
C3 (83)
001E
Auxiliary Output 1
Open in Alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
C3 (83)
001F
Alarm 1 Hysteresis H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial
setting
Summary of Contents for E5AC
Page 2: ......
Page 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Page 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Page 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Page 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Page 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...
Page 223: ......