![Omron E5AC Communications Manual Download Page 48](http://html1.mh-extra.com/html/omron/e5ac/e5ac_communications-manual_742553048.webp)
2 CompoWay/F Communications Procedures
2 - 16
E5@C Digital Temperature Controllers Communications Manual (H175)
•
Service Request PDU
•
Service Response PDU
(1) Command Code and Related Information
2-3-8
Operation Command
•
Communications Writing
•
RUN/STOP
•
Multi-SP
•
AT Execute/Cancel
•
Write Mode
•
Save RAM Data
•
Software Reset
•
Move to Setup Area 1
•
Move to Protect Level
•
Auto/Manual Switch
•
Parameter Initialization
•
Alarm Latch Cancel
•
Invert Direct/Reverse
Operation
•
Program Start
•
SP Mode
Command code
Command content
Related Information
00
Communications Writing
00: OFF (disabled)
01: ON (enabled)
01
RUN/STOP
00: Run
01: Stop
02
Multi-SP
00: Set point 0
01: Set point 1
02: Set point 2
03: Set point 3
04: Set point 4
05: Set point 5
06: Set point 6
07: Set point 7
03
AT Execute/Cancel
00: AT cancel
01: 100% AT execute
02: 40% AT execute
04
Write Mode
00: Backup
01: RAM write mode
05
Save RAM Data
00
06
Software Reset
00
07
Move to Setup Area 1
00
08
Move to Protect Level
00
09
Auto/Manual Switch
00: Automatic mode
01: Manual mode
0B
Parameter Initialization
00
MRC
SRC
3
0
0
5
2
2
2
2
Com-
mand
code
Related
informa-
tion
MRC
SRC
3
0
0
5
2
2
4
Response
code
Summary of Contents for E5AC
Page 2: ......
Page 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Page 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Page 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Page 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Page 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...
Page 223: ......