![Omron E5AC Communications Manual Download Page 49](http://html1.mh-extra.com/html/omron/e5ac/e5ac_communications-manual_742553049.webp)
2 - 17
2 CompoWay/F Communications Procedures
E5@C Digital Temperature Controllers Communications Manual (H175)
2-3 De
tailed
Descrip
tion
of
the
Ser
vices
2
2-
3-8 Oper
atio
n Command
(2) Response Code
•
Normal Completion
•
Error Occurred
(3) Operation Commands and Precautions
•
Communications Writing
Set the Communications Writing parameter to "ON: enabled" or "OFF: disabled" with the related
information setting. The setting can be accepted in both setup area 0 and setup area 1. An
operation error will occur, however, if enabling or disabling communications writing is set for an
event input.
•
RUN/STOP
Set control to “run” or “stop” with the related information setting. The setting can be accepted in
both setup area 0 and setup area 1. An operation error will occur, however, if RUN/STOP is set for
an event input.
0C
Alarm Latch Cancel
00: Alarm 1 latch cancel
01: Alarm 2 latch cancel
02: Alarm 3 latch cancel
03: HB alarm latch cancel
04: HS alarm latch cancel
05: Alarm 4 latch cancel
0F: All alarm latch cancel
0D
SP Mode
00: Local SP mode
01: Remote SP mode
0E
Invert Direct/Reverse Operation
00: Not invert
01: Invert
11
Program Start
00: Reset
01: Start
Response code
Name
Description
0000
Normal completion
No errors were found.
Response code
Error name
Description
1001
Command too long
The command is too long.
1002
Command too short
The command is too short.
1100
Parameter error
Command code and related
information are wrong.
2203
Operation error
•
The Communications Writing
parameter is set to "OFF"
(disabled). The command is
received regardless of the
Communications Writing
parameter setting (ON/OFF).
•
Processing could not be
performed. For details, refer to
(3) Operation Commands and
Precautions
below.
•
Non-volatile memory error
Command code
Command content
Related Information
Summary of Contents for E5AC
Page 2: ......
Page 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Page 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Page 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Page 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Page 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...
Page 223: ......