5 Communications Data for Modbus
5 - 12
E5@C Digital Temperature Controllers Communications Manual (H175)
Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byte
mode
0E48
2E24
Extraction of Square Root
Enable
H'00000000 (0): OFF
H'00000001 (1): ON
Initial setting
0E60
2E30
Travel Time
H'00000001 to H'000003E7 (1 to 999)
0F00
2F00
Alarm 1 Type
H'00000000 (0): Alarm function OFF
H'00000001 (1): Upper and lower-limit alarm
H'00000002 (2): Upper-limit alarm
H'00000003 (3): Lower-limit alarm
H'00000004 (4): Upper and lower-limit range alarm
H'00000005 (5): Upper and lower-limit alarm with standby sequence
H'00000006 (6): Upper-limit alarm with standby sequence
H'00000007 (7): Lower-limit alarm with standby sequence
H'00000008 (8): Absolute-value upper-limit alarm
H'00000009 (9): Absolute-value lower-limit alarm
H'0000000A (10): Absolute-value upper-limit alarm with standby
sequence
H'0000000B (11): Absolute-value lower-limit alarm with standby
sequence
H'0000000C (12): LBA (Loop Burnout Alarm)
H'0000000D (13): PV change rate alarm
H'0000000E (14): SP absolute-value upper-limit alarm
H'0000000F (15): SP absolute-value lower-limit alarm
H'00000010 (16): MV absolute-value upper-limit alarm
H'00000011 (17): MV absolute-value lower-limit alarm
H'00000012 (18): RSP absolute-value upper-limit alarm *
H'00000013 (19): RSP absolute-value lower-limit alarm *
*
Valid only with a remote SP input.
0F02
2F01
Alarm 1 Latch
H'00000000 (0): OFF
H'00000001 (1): ON
Advanced
function
setting
0F04
2F02
Alarm 1 Hysteresis
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial setting
0F06
2F03
Alarm 2 Type
H'00000000 to H'00000013 (0 to 19)
Note: Same settings as the Alarm 1 Type. However, the LBA (loop
burnout alarm) cannot be set.
0F08
2F04
Alarm 2 Latch
H'00000000 (0): OFF
H'00000001 (1): ON
Advanced
function
setting
0F0A
2F05
Alarm 2 Hysteresis
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial setting
0F0C
2F06
Alarm 3 Type
H'00000000 to H'00000013 (0 to 19)
Note: Same settings as the Alarm 1 Type. However, the LBA (loop
burnout alarm) cannot be set.
0F0E
2F07
Alarm 3 Latch
H'00000000 (0): OFF
H'00000001 (1): ON
Advanced
function
setting
0F10
2F08
Alarm 3 Hysteresis
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial setting
0F12
2F09
Alarm 4 Type
H'00000000 to H'00000013 (0 to 19)
Note: Same settings as the Alarm 1 Type. However, the LBA (loop
burnout alarm) cannot be set.
0F14
2F0A
Alarm 4 Latch
H'00000000 (0): OFF
H'00000001 (1): ON
Advanced
function
setting
0F16
2F0B
Alarm 4 Hysteresis
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial setting
0F18
2F0C
Standby Sequence Reset H'00000000 (0): Condition A
H'00000001 (1): Condition B
Advanced
function
setting
0F1A
2F0D
Auxiliary Output 1 Open
in Alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
Summary of Contents for E5AC
Page 2: ......
Page 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Page 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Page 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Page 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Page 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...
Page 223: ......