![Omron E5AC Communications Manual Download Page 47](http://html1.mh-extra.com/html/omron/e5ac/e5ac_communications-manual_742553047.webp)
2 - 15
2 CompoWay/F Communications Procedures
E5@C Digital Temperature Controllers Communications Manual (H175)
2-3 De
tailed
Descrip
tion
of
the
Ser
vices
2
2-
3-7 Echoback Test
(3) Response Code
•
Normal Completion
•
Error Occurred
This service performs an echoback test.
•
Service Request PDU
•
Service Response PDU
(1) Test Data
Set between 0 and 200 bytes of user-defined test data.
Set a value for the test data within the ranges shown below according to the communications data
length.
(2) Response Code
•
Normal Completion
•
Error Occurred
Response code
Name
Description
0000
Normal completion
No errors were found.
Response code
Error name
Description
1001
Command too long
The command is too long.
2203
Operation error
Non-volatile memory error
2-3-7
Echoback Test
Communications
data length
Test Data
8 bits
ASCII data: H'20 to H'7E or H'A1 to H'FE
7 bits
ASCII data: H'20 to H'7E
Response code
Name
Description
0000
Normal completion
No errors were found.
Response code
Error name
Description
1001
Command too long
The command is too long.
2203
Operation error
Non-volatile memory error
MRC
SRC
0
8
0
1
2
2
0 to 200
Test data
MRC
SRC
Response
code
0
8
0
1
2
2
0 to 200
Test data
4
Summary of Contents for E5AC
Page 2: ......
Page 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Page 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Page 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Page 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Page 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...
Page 223: ......