![Omron E5AC Communications Manual Download Page 62](http://html1.mh-extra.com/html/omron/e5ac/e5ac_communications-manual_742553062.webp)
3 Communications Data for CompoWay/F
3 - 8
E5@C Digital Temperature Controllers Communications Manual (H175)
Variable
type
Address
Parameter
name
Setting (monitor) value
Level
C3 (83)
0000
Input Type
H'00000000 (0):
Pt (
−
200 to 850
°
C/
−
300 to 1500°F)
H'00000001 (1):
Pt (
−
199.9 to 500.0
°
C/
−
199.9 to
900.0°F)
H'00000002 (2):
Pt (0.0 to 100.0
°
C/0.0 to 210.0°F)
H'00000003 (3):
JPt (
−
199.9 to 500.0
°
C/
−
199.9 to
900.0°F)
H'00000004 (4):
JPt (0.0 to 100.0
°
C/0.0 to 210.0°F)
H'00000005 (5):
K (
−
200 to 1300
°
C/
−
300 to 2300°F)
H'00000006 (6):
K (
−
20.0 to 500.0
°
C/0.0 to 900.0°F)
H'00000007 (7):
J (
−
100 to 850
°
C/
−
100 to 1500°F)
H'00000008 (8):
J (
−
20.0 to 400.0
°
C/0.0 to 750.0°F)
H'00000009 (9):
T (
−
200 to 400
°
C/
−
300 to 700°F)
H'0000000A (10):
T (
−
199.9 to 400.0
°
C/
−
199.9 to
700.0°F)
H'0000000B (11):
E (
−
200 to 600
°
C/
−
300 to 1100°F)
H'0000000C (12):
L (
−
100 to 850
°
C/
−
100 to 1500°F)
H'0000000D (13):
U (
−
200 to 400
°
C/
−
300 to 700°F)
H'0000000E (14):
U (
−
199.9 to 400.0
°
C/
−
199.9 to
700.0°F)
H'0000000F (15):
N (
−
200 to 1300
°
C/
−
300 to 2300°F)
H'00000010 (16):
R (0 to 1700
°
C/0 to 3000°F)
H'00000011 (17):
S (0 to 1700
°
C/0 to 3000°F)
H'00000012 (18):
B (100 to 1800
°
C/300 to 3200°F)
H'00000013 (19):
W (0 to 2300
°
C/0 to 3200°F)
H'00000014 (20):
PL II (0 to 1300
°
C/0 to 2300°F)
H'00000015 (21):
Infrared temperature sensor (K
140
°
F/60
°
C)
H'00000016 (22):
Infrared temperature sensor (K
240
°
F/120
°
C)
H'00000017 (23):
Infrared temperature sensor (K
280
°
F/140
°
C)
H'00000018 (24):
Infrared temperature sensor (K
440
°
F/220
°
C)
H'00000019 (25):
4 to 20 mA
H'0000001A (26):
0 to 20 mA
H'0000001B (27):
1 to 5 V
H'0000001C (28):
0 to 5 V
H'0000001D (29):
0 to 10 V
H'0000001E (30):
0 to 50 mV*
*
Selection is possible only for E5CC-U Controllers and
only if they are manufactured in May 2014 or later
(version 2.2).
Initial
setting
C3 (83)
0001
Scaling Upper
Limit
Scaling lower limit + 1 to H'0000270F (Scaling lower limit +
1 to 9,999)
C3 (83)
0002
Scaling Lower
Limit
H'FFFFF831 to Scaling upper limit
−
1 (
−
1999 to Scaling
upper limit
−
1)
C3 (83)
0003
Decimal Point
H'00000000 to 00000003 (0 to 3)
C3 (83)
0004
Temperature
Unit
H'00000000 (0):
°
C
H'00000001 (1): °F
C3 (83)
0005
SP Upper Limit
The range of values (without decimal point) is as follows:
Temperature input: SP lower limit + 1 to Input range upper
limit
Analog input:
SP lower limit + 1 to Scaling upper
limit
Summary of Contents for E5AC
Page 2: ......
Page 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Page 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Page 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Page 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Page 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...
Page 223: ......