6 - 83
6 Programless Communications
E5@C Digital Temperature Controllers Communications Manual (H175)
6-1
0 Con
n
ect
ing
to
MELSEC iQ-R-
series PLC
s
6
6-
10-5 Ch
ecking Op
eration
(3) To make the value easier to check, change the values that are displayed to decimal
values.
Select
View
−
Display format Detailed Setting
.
Set the display format settings shown in the following dialog box.
Set the
Display Unit Format
to
Word Multi-point
, set the
Bit Order
to
0-F
, set the
Word
Device Word Multi-point Format
to
10 Points
, and then click the
OK
Button.
The display will appear as shown below after the display format is changed.
The area where monitor values are checked is called the upload area.
D0 to D14 is the upload area for the No. 0 Controller (E5CC), D30 to D44 is the upload area
for the No. 1 Controller, and D60 to D74 is the upload area for the No. 2 Controller.
No.0
No.1
No.2