3 Communications Data for CompoWay/F
E5@C Digital Temperature Controllers Communications Manual (H175)
3-1 Variab
le Area (
S
et
tin
g
Ra
nge)
List
3
C3 (83)
0006
SP Lower Limit
The range of values (without decimal point) is as follows:
Temperature input: Input range lower limit to SP upper
limit
−
1
Analog input:
Scaling lower limit to SP upper limit
−
1
Initial
setting
C3 (83)
0007
PID ON/OFF
H'00000000 (0): ON/OFF
H'00000001 (1): 2 PID control
C3 (83)
0008
Standard or
Heating/Cooling
H'00000000 (0): Standard
H'00000001 (1): Heating and cooling
C3 (83)
0009
ST
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83)
000A
Control Period
(Heating)
H'FFFFFFFE (
−
2): 0.1 s
H'FFFFFFFF (
−
1): 0.2 s
H'00000000 (0): 0.5 s
H'00000001 to H'00000063 (1 to 99)
C3 (83)
000B
Control Period
(Cooling)
H'FFFFFFFE (
−
2): 0.1 s
H'FFFFFFFF (
−
1): 0.2 s
H'00000000 (0): 0.5 s
H'00000001 to H'00000063 (1 to 99)
C3 (83)
000C
Direct/Reverse
Operation
H'00000000 (0): Reverse operation
H'00000001 (1): Direct operation
C3 (83)
000D
Alarm 1 Type
H'00000000 (0):
Alarm function OFF
H'00000001 (1):
Upper and lower-limit alarm
H'00000002 (2):
Upper-limit alarm
H'00000003 (3):
Lower-limit alarm
H'00000004 (4):
Upper and lower-limit range alarm
H'00000005 (5):
Upper and lower-limit alarm with
standby sequence
H'00000006 (6):
Upper-limit alarm with standby
sequence
H'00000007 (7):
Lower-limit alarm with standby
sequence
H'00000008 (8):
Absolute-value upper-limit alarm
H'00000009 (9):
Absolute-value lower-limit alarm
H'0000000A (10): Absolute-value upper-limit alarm with
standby sequence
H'0000000B (11): Absolute-value lower-limit alarm with
standby sequence
H'0000000C (12): LBA (Loop Burnout Alarm)
H'0000000D (13): PV change rate alarm
H'0000000E (14): SP absolute-value upper-limit alarm
H'0000000F (15): SP absolute-value lower-limit alarm
H'00000010 (16): MV absolute-value upper-limit alarm
H'00000011 (17): MV absolute-value lower-limit alarm
H'00000012 (18): RSP absolute-value upper-limit alarm*
H'00000013 (19): RSP absolute-value lower-limit alarm*
*
Valid only with a remote SP input.
C3 (83)
000E
Alarm 2 Type
H'00000000 to H'00000013 (0 to 19)
Note: Same settings as the Alarm 1 Type. However, the
LBA (loop burnout alarm) cannot be set.
C3 (83)
000F
Alarm 3 Type
H'00000000 to H'00000013 (0 to 19)
Note: Same settings as the Alarm 1 Type. However, the
LBA (loop burnout alarm) cannot be set.
Variable
type
Address
Parameter
name
Setting (monitor) value
Level
Summary of Contents for E5AC
Page 2: ......
Page 16: ...Revision History 14 E5 C Digital Temperature Controllers Communications Manual H175...
Page 22: ...20 E5 C Digital Temperature Controllers Communications Manual H175...
Page 214: ...7 Component Communications 7 8 E5 C Digital Temperature Controllers Communications Manual H175...
Page 219: ...I 1 E5 C Digital Temperature Controllers Communications Manual H175 I Index...
Page 222: ...I 4 E5 C Digital Temperature Controllers Communications Manual H175...
Page 223: ......