7-2
CompoWay/F Slaves Connected to a PLC
7-2-1
Communications with CompoWay/F Slaves through a PLC
7-2
CompoWay/F Slaves Connected to a PLC
7-2-1
Communications with CompoWay/F Slaves through a PLC
Use the following procedures to transfer network information of CompoWay/F Slaves
connected to a serial port of a CS/CJ-series CPU Unit or Serial Communications
Board/Unit, or serial port C on the Controller Section of an NSJ-series NSJ Controller.
Example: In the following example, an E5CN Temperature Controller is connected to
port 1 (RS-422/RS-485 port) of a CJ1W-SCU41-V1 Serial
Communications Unit with the CompoWay/F protocol.
Before Connecting by CompoWay/F Protocol
Before connecting by the CompoWay/F protocol, edit the CJ1W-SCU41-V1 Unit’s
parameters to set the serial port 1
Serial communications mode
to
Serial Gateway
.
1. Right-click the Serial Communications Unit in the I/O table and select
Unit Setup
.
The Edit Parameters Dialog Box will be displayed.
2. Set the
Port1: Port settings
set value to
User settings
.
3. Set the
Port1: Serial communications mode
set value to
Serial Gateway
.
2. Set to
User settings
.
3. Set the
Serial communications mode
to
Serial Gateway
.
Example: Unit settings for a Serial
Communications Unit/Board
7-3
Summary of Contents for CX-INTEGRATOR - V1.1
Page 1: ...OPERATION MANUAL CX Integrator Ver 1 1 SYSMAC CXONE AL C E Cat No W445 E1 02...
Page 2: ...CXONE AL C E CX Integrator Ver 1 1 Operation Manual Revised November 2005...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 120: ...Communications Section 3 Routing Tables This section describes how to set the routing tables 3...
Page 200: ...Communications Section 5 Ethernet This section describes the operations specific to Ethernet 5...
Page 328: ...Appendices A...
Page 336: ......